FIR10-00146
| INSP-Sprinkler Rough-in | 6/23/2010 | 6/23/2010 | 6/24/2010 11:40:32 AM | P | PART |
|
|
To confirm work in progress for vanilla building permit final BLD10-00508.
|
FIR10-00228
| INSP-Sprinkler Rough-in | 6/23/2010 | 6/23/2010 | 6/24/2010 11:38:34 AM | P | PART |
|
|
Overhead rough-in okayed for cover.
|
BLD10-00831
| FIRE-Conference | 6/22/2010 | 6/23/2010 | 6/23/2010 4:10:06 PM | P | DONE |
|
|
On site visit regarding fire life safety requirements. Noted fire alarm and sprinkler contractors have commenced work without issued permits- double fees will apply. A stop work order may be applied if work continues without authorization.
|
FIR05-00533
| FIR-Aging Inspection | 6/23/2010 | 6/23/2010 | 6/23/2010 2:53:26 PM | | DONE |
|
|
|
FIR10-00125
| FIR-Aging Inspection | 6/23/2010 | 6/23/2010 | 6/23/2010 2:52:40 PM | | DONE |
|
|
Site work in progress
|
FIR08-00678
| FIR-Aging Inspection | 6/23/2010 | 6/23/2010 | 6/23/2010 2:51:23 PM | | PEND |
|
|
Work in progress
|
BLD10-00813
| FIRE-Final Inspection | 6/22/2010 | 6/23/2010 | 6/23/2010 2:47:09 PM | P | FAIL |
|
|
The main entry/exit door is equipped with a manual thumbturn. See plan review notes for details pertaining.
|
BLD10-00797
| FIRE-Final Inspection | 6/22/2010 | 6/23/2010 | 6/23/2010 2:45:22 PM | P | PASS |
|
|
Correction items per last site visit finished, inspection passed. No signature card available on site.
|
BLD10-00973
| FIRE-Final Inspection | 6/23/2010 | 6/23/2010 | 6/23/2010 2:19:14 PM | P | NR |
|
|
marty Phone #: ###-#### NOTE: Project is not in condition for final- framing and trade rough-ins only at this time. Phoned contractor- no answer.
|
BLD10-00661
| FIRE-Final Inspection | 6/22/2010 | 6/23/2010 | 6/23/2010 2:16:40 PM | A | FAIL |
|
|
Access-controlled egress doors must be in compliance with IFC sec. 1008.1.3.4. Also noted two non-functional EM lights. Remainder of life safety items appear satisfactory.
|
BLD06-01629
| FIRE-Final Inspection | 6/22/2010 | 6/23/2010 | 6/23/2010 2:14:06 PM | A | FAIL |
|
|
Provide approved door hardware at the main entry/exit.
|
BLD05-03074
| FIRE-Final Inspection | 6/22/2010 | 6/23/2010 | 6/23/2010 2:12:30 PM | A | FAIL |
|
|
Relocate one exit sign per plan as discussed.
|
BLD10-00991
| FIRE-Conference | 6/22/2010 | 6/23/2010 | 6/23/2010 1:31:31 PM | A | DONE |
|
|
Site visit regarding fire life safety related conditions for occupancy approval including door hardware, exit signs/EM lights, fire extinguishers, type one hood suppression, etc.
|
FIR10-00248
| INSP-Alarm Testing | 6/22/2010 | 6/23/2010 | 6/23/2010 1:27:39 PM | A | PART |
|
|
Functional testing completed for new mag locks at two locations. Noted knox box needs to be relocated from behind the new enclosure, need to review building permit documents related to the construction of the new gates for verification of code compliance related to egress, door swing, etc.
|