Inspections for the day of: Wednesday, June 23, 2010.
Number of inspections: 14
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorForrest France
TitleFIRE INSPECTOR
Phone #794-1981
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
FIR10-00146 INSP-Sprinkler Rough-in6/23/20106/23/20106/24/2010 11:40:32 AMPPART
To confirm work in progress for vanilla building permit final BLD10-00508.
FIR10-00228 INSP-Sprinkler Rough-in6/23/20106/23/20106/24/2010 11:38:34 AMPPART
Overhead rough-in okayed for cover.
BLD10-00831 FIRE-Conference6/22/20106/23/20106/23/2010 4:10:06 PMPDONE
On site visit regarding fire life safety requirements. Noted fire alarm and sprinkler contractors have commenced work without issued permits- double fees will apply. A stop work order may be applied if work continues without authorization.
FIR05-00533 FIR-Aging Inspection6/23/20106/23/20106/23/2010 2:53:26 PM DONE
FIR10-00125 FIR-Aging Inspection6/23/20106/23/20106/23/2010 2:52:40 PM DONE
Site work in progress
FIR08-00678 FIR-Aging Inspection6/23/20106/23/20106/23/2010 2:51:23 PM PEND
Work in progress
BLD10-00813 FIRE-Final Inspection6/22/20106/23/20106/23/2010 2:47:09 PMPFAIL
The main entry/exit door is equipped with a manual thumbturn. See plan review notes for details pertaining.
BLD10-00797 FIRE-Final Inspection6/22/20106/23/20106/23/2010 2:45:22 PMPPASS
Correction items per last site visit finished, inspection passed. No signature card available on site.
BLD10-00973 FIRE-Final Inspection6/23/20106/23/20106/23/2010 2:19:14 PMPNR
marty Phone #: ###-#### NOTE: Project is not in condition for final- framing and trade rough-ins only at this time. Phoned contractor- no answer.
BLD10-00661 FIRE-Final Inspection6/22/20106/23/20106/23/2010 2:16:40 PMAFAIL
Access-controlled egress doors must be in compliance with IFC sec. 1008.1.3.4. Also noted two non-functional EM lights. Remainder of life safety items appear satisfactory.
BLD06-01629 FIRE-Final Inspection6/22/20106/23/20106/23/2010 2:14:06 PMAFAIL
Provide approved door hardware at the main entry/exit.
BLD05-03074 FIRE-Final Inspection6/22/20106/23/20106/23/2010 2:12:30 PMAFAIL
Relocate one exit sign per plan as discussed.
BLD10-00991 FIRE-Conference6/22/20106/23/20106/23/2010 1:31:31 PMADONE
Site visit regarding fire life safety related conditions for occupancy approval including door hardware, exit signs/EM lights, fire extinguishers, type one hood suppression, etc.
FIR10-00248 INSP-Alarm Testing6/22/20106/23/20106/23/2010 1:27:39 PMAPART
Functional testing completed for new mag locks at two locations. Noted knox box needs to be relocated from behind the new enclosure, need to review building permit documents related to the construction of the new gates for verification of code compliance related to egress, door swing, etc.