Inspections for the day of: Thursday, June 23, 2011.
Number of inspections: 9
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorDaryl DeGrange
TitleELE-INSPECTION SUPV
Phone #794-1379
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
ELE11-00265 Final6/22/20116/23/20116/23/2011 3:02:00 PMPPASS
Call Craig Timmons if you have any questions. Phone #: ###-#### >> Inspection requested via web by Vicki Moore final ok
ELE11-01330 Electrical Rough-In6/23/20116/23/20116/23/2011 2:14:40 PMPPASS
Re-inspect of the south wall only. Contact is Jay Sprik. Phone #: ###-#### >> Inspection requested via web by Richard Montgomery rough-in ok cover south wall only.
ELE11-01334 Electrical Rough-In6/23/20116/23/20116/23/2011 1:48:43 PMPPASS
Geoff Hannaford-contact-###-####-Wall Inspection Phone #: ###-#### >> Inspection requested via web by Debby Ellis rough-in ok cover walls
ELE11-01335 Rough-In Permanent Service6/23/20116/23/20116/23/2011 12:02:45 PMPPASS
Phone #: ###-#### >> Inspection requested via web by daniel bibikov rough-in ok but no permanent service- overhead service mask needs to be at least 2 in IMC if going to be point of attachment.
ELE11-01330 Electrical Rough-In6/22/20116/23/20116/23/2011 10:24:04 AMAFAIL
This is a partial wall inspection only. Please inspect the south wall (the wall commons the hair cutting place). Contact is Jay Sprik. Phone #: ###-#### >> Inspection requested via web by Richard Montgomery NEC 330.12 shall not be installed were subject to physical damage. Inside framing member (steel studs)
ELE09-00326 Final6/22/20116/23/20116/23/2011 9:40:16 AMAFAIL
kathy Phone #: ###-#### - please call 1/2 hr prior NEC 408.7 unsued openings in panel shall be closed using identified closures. A/C unit requires proper ampage breaker
GCE11-00046 GCE-Permanent Service6/22/20116/23/20116/23/2011 9:00:41 AMAPASS
Perm ServiceTodd @ ###-####Call in advance p/s u/g rec ok
GCE11-00053 GCE-Rough-In6/22/20116/23/20116/23/2011 8:56:21 AMAFAIL
Rough-InAaron @ ###-####Call for access NEC 210.(A) (2) Receptacle spacing 7 locations- attic stapling every 4 1/2 ft NEC300.4(D) Stapling 1 1/4 from edge of framing member
GCE11-00068 GCE-Permanent Service6/22/20116/23/20116/23/2011 8:09:59 AMAPASS
Perm ServiceWarren @ ###-#### p/s o/h rec ok