Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
ELE12-02616 ELE-Aging Inspection6/23/20146/23/20146/26/2014 2:39:03 PM DONE
Spoke with electrical contractor, discussed required final inspection.
ELE13-02849 Electrical Rough-In6/23/20146/23/20146/23/2014 1:12:15 PMPPASS
Contact is Alan Krishnek - ceiling cover inspection Phone #: ###-#### >> Inspection requested via web by Scott Campbell rough-in ok cover ceiling grid interview stations
ELE14-01616 Electrical Rough-In6/19/20146/23/20146/23/2014 12:44:18 PMPPASS
Jake is the contact his cell no. is ###-####. Phone #: ###-#### >> Inspection requested via web by Mike Basye rough-in ok cover four half walls in biology labs,teacher station
ELE14-01594 Temporary Service6/23/20146/23/20146/23/2014 12:06:10 PMPPASS
Phone #: ###-#### >> Inspection requested via web by Alan Lusk t/s u/g n ok
ELE14-01440 Final6/19/20146/23/20146/23/2014 11:59:40 AMPPART
There is another inspection for same location I am going to schedule for Monday also. Permit #BLD14-00699 Phone #: ###-#### >> Inspection requested via web by Sheri Lewis NEC 210.8(B)5 Recepticals within six feet of water basin require GFCI portection
ELE14-01641 Electrical Rough-In6/23/20146/23/20146/23/2014 10:49:38 AMPPASS
Call 8703080 for any questions Phone #: ###-#### >> Inspection requested via web by Jerry Moore rough-in ok cover
ELE12-02592 ELE-Aging Inspection6/23/20146/23/20146/23/2014 10:30:49 AM DONE
contractor will check into matter
ELE14-01637 Final6/21/20146/23/20146/23/2014 9:49:16 AMAFAIL
This Is A Idaho Power Lighting Upgrade And We Changed All Outlets To Tamperproof As Well As New Led E-Lights And Exit Signs On Existing Openings. Please Call Joe At ###-####. Thanks And Have A Great Day! Phone #: ###-#### >> Inspection requested via web by jason shifflett Lighting retros require rough-in inspections to check listed material. Bathroom GFCI has reverse polarity NEC 422.52 Drinking fountains require GFCI protection. End cap in florscent fixture requires KO seal
ELE14-01169 Electrical Rough-In6/20/20146/23/20146/23/2014 9:11:35 AMAFAIL
Phone #: ###-#### >> Inspection requested via web by David Nelson NEC 300.4 Nail plates required where NM cable are less than 1 1/4 from edge of framing member( either side) NEC 334.30 Shall secure cable within 12 in. of entering service panel NEC 334.80 Shall not staple more than 3 NM cables together(stackets)
ELE14-01635 Final6/20/20146/23/20146/23/2014 8:40:53 AMAFAIL
Wired new heat pump, any questions call Andy @ ###-#### Phone #: ###-#### >> Inspection requested via web by Andy Rose NEC 110.26 Working space for service gear. Unit placed to close to service pedistal
ELE14-01634 Electrical Rough-In6/20/20146/23/20146/23/2014 8:17:08 AMAPASS
Chris Phone #: ###-#### rough-in ok cover front soffit
ELE14-00963 Final6/23/20146/23/20146/23/2014 7:58:59 AMAPASS
Call Ben if any questions Phone #: ###-#### >> Inspection requested via web by Ben Archibald Nice job final ok
ELE14-01169 Final6/20/20146/23/20146/20/2014 4:00:07 PMACANC
Phone #: ###-#### >> Inspection requested via web by David Nelson Inspection cancelled from web by: David Nelson