Inspections for the day of: Thursday, June 23, 2016.
Number of inspections: 15
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorJim Page
TitleFIRE INSPECTOR
Phone #208-914-5431
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
FIR16-00408 INSP-Sprinkler Rough-in6/23/20166/23/20166/23/2016 3:03:00 PMPPASS
Rough to cover inspection for underground supply complete, underground piping approved for cover.
BLD16-00129 FIRE-Final Inspection6/22/20166/23/20166/23/2016 2:50:48 PMPFAIL
Sprinkler head in south side of new conference room is over spaced, sprinkler head in receptionist area is over spaced. $ interior doors still have round knob type door hardware, needs to be changed to paddle type door handle hardware.
BLD15-04191 FIRE-Final Inspection6/23/20166/23/20166/23/2016 2:16:10 PMPPART
Level 1 fire sprinklers complete, level 1 fire alarms complete, level 1 fire extinguishers are in place with current inspection tags. Life fire safety complete for level 1 excluding smoke evacuation system and elevator smoke curtains, when smoke evac and curtians have been inspected/passed then life fire safety can be finaled.
FIR16-00212 INSP-Final Inspection6/21/20166/23/20166/23/2016 2:10:44 PMPPASS
Final fire sprinkler inspection passed/complete
FIR15-00767 INSP-Alarm Testing6/22/20166/23/20166/23/2016 12:48:51 PMADONE
Alarm testing complete, all devices with the new fire alarm system has been tested. A 10% functionality test will be performed on the new fire alarm system after the old fire alarm system and components have been removed. Note that the 5th floor pre-action isolation valve has a visible leak on the valve (leaks in the fire sprinkler system has the potential to cause false alarms), leak needs to be repaired before fire alarm system will by signed off as complete,
BLD16-00185 FIRE-Final Inspection6/22/20166/23/20166/23/2016 10:38:58 AMAPASS
Fire sprinkler inspection complete (FIR16-00150, FIR perimit is not attached to this project) no fire alarm modifications, fire extinguishers are in place with current inspection tags. Final life fire safety inspection passed/complete.
FIR16-00150 INSP-Final Inspection6/23/20166/23/20166/23/2016 10:36:31 AMAPASS
Final fire sprinkler inspection passed/complete
FIR15-00806 INSP-Sprinkler Rough-in/Hydro6/22/20166/23/20166/23/2016 10:01:20 AMAPASS
Level 2 hydrostatic test for overhead fire sprinkler piping complete.
BLD16-02132 FIRE-Final Inspection6/22/20166/23/20166/23/2016 9:59:08 AMAPASS
Fire sprinkler inspection is current, fire alarm inspection is current, fire extinguishers are in place with current inspection tags. Final life fire safety inspection passed/complete.
BLD16-01912 FIRE-Final Inspection6/23/20166/23/20166/23/2016 9:50:03 AMPPASS
Fire sprinkler inspection complete, no fire alarm modifications, fire extinguishers are in place with current inspection tags. Final life fire safety inspection passed/complete.
FIR16-00398 INSP-Final Inspection6/23/20166/23/20166/23/2016 9:48:49 AMPPASS
Final fire sprinkler inspection passed/complete
BLD16-01621 FIRE-Final Inspection6/22/20166/23/20166/23/2016 9:27:39 AMAPASS
No fire sprinklers, no fire alam modifications, fire extinguisher is in place with current inspection tag. Final life fire safety inspection passed/complete.
BLD16-02069 FIRE-Final Inspection6/22/20166/23/20166/23/2016 9:06:36 AMAPASS
No fire sprinklers, no fire alarms, fire extinguisher is in place with current inspection tag, no upgrade to door hardware, noted that rear exit door has thumb-turn deadbolt hardware. Final life fire safety inspection passed/complete.
FIR16-00143 INSP-Sprinkler Rough-in6/22/20166/23/20166/23/2016 8:55:39 AMAPASS
Rough to cover inspection for overhead fire sprinklers complete, notated city approved drawings area's approved for cover.
FIR15-00806 INSP-Sprinkler Rough-in6/22/20166/23/20166/23/2016 8:28:08 AMAPASS
Rough to cover inspection for overhead fire sprinkler piping on level 2 complete, level 2 overhead fire sprinkler piping approved for cover.