FIR16-00408
| INSP-Sprinkler Rough-in | 6/23/2016 | 6/23/2016 | 6/23/2016 3:03:00 PM | P | PASS |
|
|
Rough to cover inspection for underground supply complete, underground piping approved for cover.
|
BLD16-00129
| FIRE-Final Inspection | 6/22/2016 | 6/23/2016 | 6/23/2016 2:50:48 PM | P | FAIL |
|
|
Sprinkler head in south side of new conference room is over spaced, sprinkler head in receptionist area is over spaced. $ interior doors still have round knob type door hardware, needs to be changed to paddle type door handle hardware.
|
BLD15-04191
| FIRE-Final Inspection | 6/23/2016 | 6/23/2016 | 6/23/2016 2:16:10 PM | P | PART |
|
|
Level 1 fire sprinklers complete, level 1 fire alarms complete, level 1 fire extinguishers are in place with current inspection tags. Life fire safety complete for level 1 excluding smoke evacuation system and elevator smoke curtains, when smoke evac and curtians have been inspected/passed then life fire safety can be finaled.
|
FIR16-00212
| INSP-Final Inspection | 6/21/2016 | 6/23/2016 | 6/23/2016 2:10:44 PM | P | PASS |
|
|
Final fire sprinkler inspection passed/complete
|
FIR15-00767
| INSP-Alarm Testing | 6/22/2016 | 6/23/2016 | 6/23/2016 12:48:51 PM | A | DONE |
|
|
Alarm testing complete, all devices with the new fire alarm system has been tested. A 10% functionality test will be performed on the new fire alarm system after the old fire alarm system and components have been removed. Note that the 5th floor pre-action isolation valve has a visible leak on the valve (leaks in the fire sprinkler system has the potential to cause false alarms), leak needs to be repaired before fire alarm system will by signed off as complete,
|
BLD16-00185
| FIRE-Final Inspection | 6/22/2016 | 6/23/2016 | 6/23/2016 10:38:58 AM | A | PASS |
|
|
Fire sprinkler inspection complete (FIR16-00150, FIR perimit is not attached to this project) no fire alarm modifications, fire extinguishers are in place with current inspection tags. Final life fire safety inspection passed/complete.
|
FIR16-00150
| INSP-Final Inspection | 6/23/2016 | 6/23/2016 | 6/23/2016 10:36:31 AM | A | PASS |
|
|
Final fire sprinkler inspection passed/complete
|
FIR15-00806
| INSP-Sprinkler Rough-in/Hydro | 6/22/2016 | 6/23/2016 | 6/23/2016 10:01:20 AM | A | PASS |
|
|
Level 2 hydrostatic test for overhead fire sprinkler piping complete.
|
BLD16-02132
| FIRE-Final Inspection | 6/22/2016 | 6/23/2016 | 6/23/2016 9:59:08 AM | A | PASS |
|
|
Fire sprinkler inspection is current, fire alarm inspection is current, fire extinguishers are in place with current inspection tags. Final life fire safety inspection passed/complete.
|
BLD16-01912
| FIRE-Final Inspection | 6/23/2016 | 6/23/2016 | 6/23/2016 9:50:03 AM | P | PASS |
|
|
Fire sprinkler inspection complete, no fire alarm modifications, fire extinguishers are in place with current inspection tags. Final life fire safety inspection passed/complete.
|
FIR16-00398
| INSP-Final Inspection | 6/23/2016 | 6/23/2016 | 6/23/2016 9:48:49 AM | P | PASS |
|
|
Final fire sprinkler inspection passed/complete
|
BLD16-01621
| FIRE-Final Inspection | 6/22/2016 | 6/23/2016 | 6/23/2016 9:27:39 AM | A | PASS |
|
|
No fire sprinklers, no fire alam modifications, fire extinguisher is in place with current inspection tag. Final life fire safety inspection passed/complete.
|
BLD16-02069
| FIRE-Final Inspection | 6/22/2016 | 6/23/2016 | 6/23/2016 9:06:36 AM | A | PASS |
|
|
No fire sprinklers, no fire alarms, fire extinguisher is in place with current inspection tag, no upgrade to door hardware, noted that rear exit door has thumb-turn deadbolt hardware. Final life fire safety inspection passed/complete.
|
FIR16-00143
| INSP-Sprinkler Rough-in | 6/22/2016 | 6/23/2016 | 6/23/2016 8:55:39 AM | A | PASS |
|
|
Rough to cover inspection for overhead fire sprinklers complete, notated city approved drawings area's approved for cover.
|
FIR15-00806
| INSP-Sprinkler Rough-in | 6/22/2016 | 6/23/2016 | 6/23/2016 8:28:08 AM | A | PASS |
|
|
Rough to cover inspection for overhead fire sprinkler piping on level 2 complete, level 2 overhead fire sprinkler piping approved for cover.
|