FIR17-00135
| INSP-Final Inspection | 6/22/2017 | 6/23/2017 | 6/23/2017 2:19:24 PM | P | PART |
|
|
Final inspection complete for overhead fire sprinkler system. Items to be addressed before final life fire safety inspection: Upright head that is located to far down from the ceiling in wash room needs to be removed, head in cooler area next to the bar has overspray paint on the glass bulb (sprinkler head cannot be cleaned, sprinkler head must be replaced), wires hanging/attached to main and branch lines in south corridor cannot be attached to sprinkler piping and need to be supported on thier own hangers.
|
BLD16-01617
| FIRE-Final Inspection | 6/23/2017 | 6/23/2017 | 6/23/2017 2:13:35 PM | P | PASS |
|
|
Final inspection for fire life safety passed/complete
|
BLD16-02412
| FIRE-Sprinkler Rough-in | 6/23/2017 | 6/23/2017 | 6/23/2017 10:55:38 AM | P | CANC |
|
|
Comments for Fire Sprinkler Tenting Inspection Under Permit FIR16-00790
|
FIR16-00790
| INSP-Sprinkler Rough-in | 6/23/2017 | 6/23/2017 | 6/23/2017 10:54:38 AM | P | PASS |
|
|
Tenting inspection complete, overhead fire sprinkler piping approved for cover.
|
FIR17-00153
| INSP-Sprinkler Rough-in/Hydro | 6/22/2017 | 6/23/2017 | 6/23/2017 10:40:37 AM | A | PASS |
|
|
Rough to cover inspection complete, approved for cover. Hydrostatic testing for area of work complete.complete
|
BLD15-01125
| FIRE-Final Inspection | 6/22/2017 | 6/23/2017 | 6/23/2017 10:39:08 AM | A | PASS |
|
|
Fire sprinkler inspection complete, fire alarm inspection complete, fire extinguishers are in place with current inspection tags, building has knox box installed. Final life fire safey inspection passed/complete.
|
BLD17-01766
| FIRE-Final Inspection | 6/23/2017 | 6/23/2017 | 6/23/2017 10:09:19 AM | P | PASS |
|
|
FInal life fire safety inspection passed/complete
|
FIR17-00289
| INSP-Sprinkler Rough-in | 6/22/2017 | 6/23/2017 | 6/23/2017 9:55:06 AM | A | PASS |
|
|
Rough to cover inspection fore overhead fire sprinkler piping in area of work complete, approved for cover.
|
FIR17-00057
| INSP-Sprinkler Rough-in/Hydro | 6/22/2017 | 6/23/2017 | 6/23/2017 9:42:36 AM | A | PASS |
|
|
Rough to cover inspection complete, approved for cover. Hydrostatic test for overhead fire sprinkler piping complete.
|
FIR16-00808
| INSP-Sprinkler Rough-in/Hydro | 6/22/2017 | 6/23/2017 | 6/23/2017 9:41:31 AM | A | PASS |
|
|
Rough to cover inspection complete, approved for cover. Hydrostatic test for overhead fire sprinkler piping complete.
|
FIR16-00299
| INSP-Sprinkler Rough-in | 6/22/2017 | 6/23/2017 | 6/23/2017 9:23:32 AM | A | PART |
|
|
Rough to cover inspection for overhead fire sprinkler piping/pendant heads located in the corridors on 4th-8th floors complete, approved for cover, pool area and rooms attached to pool area approved for cover.
|
FIR17-00144
| INSP-Sprinkler Rough-in/Hydro | 6/22/2017 | 6/23/2017 | 6/23/2017 9:20:15 AM | A | CANC |
|
|
Inspection request cancelled per conversation with point of contact, Jake Phone #: ###-####, inspection will be rescheduled for a later date.
|
FIR16-00697
| INSP-Sprinkler Rough-in | 6/21/2017 | 6/23/2017 | 6/23/2017 7:13:18 AM | A | CANC |
|
|
Pipe and tenting Phone #: ###-#### >> Inspection requested via web by Sam Ball Inspection cancelled from web by: Sam Ball
|
BLD17-01176
| FIRE-Final Inspection | 6/22/2017 | 6/23/2017 | 6/23/2017 12:00:00 AM | A | CANC |
|
|
Russ-can you do as early as possible so the building final can be done as late as possible Phone #: ###-####-after talking to Jim Page-we think the inspection was scheduled for the wrong address and/or permit #-Called Russ to make sure his inspection was done-he's said everything was fine
|