Inspections for the day of: Tuesday, June 24, 2003.
Number of inspections: 14
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorJack Frank
TitleELE-INSPECTOR
Phone #794-1930
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
ELE00-04214 ELE-Aging Inspection6/24/20036/24/20036/24/2003 12:00:00 AM CANC
bld is expired 6/24/2003 10:29:01 AM
ELE00-04299 ELE-Aging Inspection6/24/20036/24/20036/24/2003 12:00:00 AM CANC
bld is expired 6/24/2003 10:27:47 AM
ELE03-01840 Permanent Service6/20/20036/24/20036/24/2003 12:00:00 AMAPASS
###-#### p/s u/g rec. ok 6/24/2003 11:09:32 AM
ELE03-01849 Rough-In Permanent Service6/23/20036/24/20036/24/2003 12:00:00 AMAFAIL
###-#### terri cor. posted called 250.32 (B)(1) isolate grds and neuts garage p/s, 250.104 bond hot and cold at house, 250.53 (D)(2) garage needs 2 grd rods,, also remove grd wire from sub panel in basement 6/24/2003 9:32:47 AM
ELE03-01718 Electrical Rough-In6/23/20036/24/20036/24/2003 12:00:00 AMAPART
Scheduled by a contractor via Hello! on 6/23/2003 at 11:33:45 AM. Contact: ###-####. u/g ok print high lighted for area inspected 6/24/2003 10:23:52 AM
ELE03-01088 Final6/23/20036/24/20036/24/2003 12:00:00 AMAPASS
Scheduled by a contractor via Hello! on 6/23/2003 at 1:29:14 PM. Contact: ###-####.
ELE03-00894 Final6/23/20036/24/20036/24/2003 12:00:00 AMAPASS
Scheduled by a contractor via Hello! on 6/23/2003 at 1:32:52 PM. Contact: ###-####.
ELE03-01871 Final6/23/20036/24/20036/24/2003 12:00:00 AMAPASS
###-#### terri replaced broken 2 inch hub at p/s, and mast 6/24/2003 2:02:50 PM
ELE03-00477 Final6/24/20036/24/20036/24/2003 12:00:00 AMAPASS
ELE02-01900 ELE-Request for Extension6/24/20036/24/20036/24/2003 12:00:00 AMPPASS
###-#### blaine ok 6/24/2003 1:13:18 PM
ELE02-01900 Final6/24/20036/24/20036/24/2003 12:00:00 AMPPASS
###-#### blaine ok 6/24/2003 1:41:26 PM
ELE01-03617 Electrical Rough-In6/24/20036/24/20036/24/2003 12:00:00 AMPPART
dennis; Phone #: ###-#### Internet Inspection Request from: Barbara Moore u/G and electrode ok 6/24/2003 2:42:37 PM
ELE03-00057 Electrical Rough-In6/24/20036/24/20036/24/2003 12:00:00 AMPPART
alan; Phone #: ###-#### Internet Inspection Request from: Annette Moore u/g pole lights 6/24/2003 3:45:08 PM
ELE03-01873 Rough-In Permanent Service6/24/20036/24/20036/24/2003 12:00:00 AMPPASS
###-#### zane r/i ok

p/s u/g new ok 6/24/2003 4:33:13 PM