FIR00-00480
| FIR-Aging Inspection | 6/24/2003 | 6/24/2003 | 6/24/2003 12:00:00 AM | | PASS |
|
|
Inspector 406 gave the building a OK for perm occupancy under the building permit history 6/24/2003 8:45:24 AM
|
FIR03-00234
| INSP-Final Inspection | 6/20/2003 | 6/24/2003 | 6/24/2003 12:00:00 AM | A | FAIL |
|
|
Provide as built drawings of the system. Identify the two pull stations with the correct hood suppression system. Provide baffle between the wok that is being used as a deep fryer and the open burner that is atleast 8" high and move the fryer under the hood 6" 6/24/2003 10:47:05 AM
|
BLD03-01262
| FIRE-Conference | 6/23/2003 | 6/24/2003 | 6/24/2003 12:00:00 AM | A | CANC |
|
|
BOB; Phone #: ###-#### Internet Inspection Request from: Darla Downs
|
FIR03-00177
| INSP-Sprinkler Rough-in/Hydro | 6/24/2003 | 6/24/2003 | 6/24/2003 12:00:00 AM | P | PASS |
|
|
24 hour air test on the dry system passed 6/24/2003 4:44:51 PM
|
FIR03-00177
| INSP-Sprinkler Rough-in/Hydro | 6/24/2003 | 6/24/2003 | 6/24/2003 12:00:00 AM | P | FAIL |
|
|
pressure test on the wet system failed
|