Inspections for the day of: Tuesday, June 24, 2003.
Number of inspections: 5
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorTroy Cobbley
TitleFIRE INSPECTOR
Phone #794-9483
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
FIR00-00480 FIR-Aging Inspection6/24/20036/24/20036/24/2003 12:00:00 AM PASS
Inspector 406 gave the building a OK for perm occupancy under the building permit history 6/24/2003 8:45:24 AM
FIR03-00234 INSP-Final Inspection6/20/20036/24/20036/24/2003 12:00:00 AMAFAIL
Provide as built drawings of the system. Identify the two pull stations with the correct hood suppression system. Provide baffle between the wok that is being used as a deep fryer and the open burner that is atleast 8" high and move the fryer under the hood 6" 6/24/2003 10:47:05 AM
BLD03-01262 FIRE-Conference6/23/20036/24/20036/24/2003 12:00:00 AMACANC
BOB; Phone #: ###-#### Internet Inspection Request from: Darla Downs
FIR03-00177 INSP-Sprinkler Rough-in/Hydro6/24/20036/24/20036/24/2003 12:00:00 AMPPASS
24 hour air test on the dry system passed 6/24/2003 4:44:51 PM
FIR03-00177 INSP-Sprinkler Rough-in/Hydro6/24/20036/24/20036/24/2003 12:00:00 AMPFAIL
pressure test on the wet system failed