Inspections for the day of: Thursday, June 24, 2004.
Number of inspections: 5
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorTroy Cobbley
TitleFIRE INSPECTOR
Phone #794-9483
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
FIR04-00162 INSP-Alarm Testing6/23/20046/24/20046/24/2004 12:00:00 AMAFAIL
Repair horns in rooms 201 and 104. Repair flow switch. Provide signage on door to riser and facp. 6/24/2004 2:51:33 PM
FIR03-00571 INSP-Final Inspection6/24/20046/24/20046/24/2004 12:00:00 AMPPASS
Underground permit finaled
FIR03-00669 INSP-Final Inspection6/24/20046/24/20046/24/2004 12:00:00 AMPFAIL
All items on the correction notice have been corrected. Overhead hydro test is complete. Still need to verify that all canopies are installed and that spacing is ok. Pendant head in admin. office is too far down from ceiling.
FIR04-00260 INSP-Final Inspection6/23/20046/24/20046/24/2004 12:00:00 AMPFAIL
Fire alarm panel was not operating and is not on a dedicated circuit 6/24/2004 4:03:22 PM
FIR04-00011 INSP-Final Inspection6/23/20046/24/20046/24/2004 12:00:00 AMPFAIL
Resubmit plans showing additional devices. Backflow preventors to annunciate separately. Provide in-duct detectors instead of duct detectors at the fire/smoke dampers. Smoke detectors are over spaced in hall 165, library and outside of the admin. office. Provide signage on fire sprinkler riser door. No notification devices have been verified for spacing or function. 6/24/2004 3:08:35 PM