FIR04-00162
| INSP-Alarm Testing | 6/23/2004 | 6/24/2004 | 6/24/2004 12:00:00 AM | A | FAIL |
|
|
Repair horns in rooms 201 and 104. Repair flow switch. Provide signage on door to riser and facp. 6/24/2004 2:51:33 PM
|
FIR03-00571
| INSP-Final Inspection | 6/24/2004 | 6/24/2004 | 6/24/2004 12:00:00 AM | P | PASS |
|
|
Underground permit finaled
|
FIR03-00669
| INSP-Final Inspection | 6/24/2004 | 6/24/2004 | 6/24/2004 12:00:00 AM | P | FAIL |
|
|
All items on the correction notice have been corrected. Overhead hydro test is complete. Still need to verify that all canopies are installed and that spacing is ok. Pendant head in admin. office is too far down from ceiling.
|
FIR04-00260
| INSP-Final Inspection | 6/23/2004 | 6/24/2004 | 6/24/2004 12:00:00 AM | P | FAIL |
|
|
Fire alarm panel was not operating and is not on a dedicated circuit 6/24/2004 4:03:22 PM
|
FIR04-00011
| INSP-Final Inspection | 6/23/2004 | 6/24/2004 | 6/24/2004 12:00:00 AM | P | FAIL |
|
|
Resubmit plans showing additional devices. Backflow preventors to annunciate separately. Provide in-duct detectors instead of duct detectors at the fire/smoke dampers. Smoke detectors are over spaced in hall 165, library and outside of the admin. office. Provide signage on fire sprinkler riser door. No notification devices have been verified for spacing or function. 6/24/2004 3:08:35 PM
|