Inspections for the day of: Friday, June 24, 2005.
Number of inspections: 14
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorBob Reichert
TitleELE-INSPECTOR
Phone #794-1923
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
ELE05-01399 Electrical Rough-In6/24/20056/24/20056/24/2005 4:15:32 PMPPART
Scheduled by a contractor via Hello! on 6/24/2005 at 7:40:42 AM. Contact: ###-####. bathroom lids and walls ok, north 1/2 building walls only ok to cover
ELE05-01620 Final6/24/20056/24/20056/24/2005 4:05:51 PMPPASS
ed; Phone #: ###-#### Internet Inspection Request from: Letitia Mesa corrections made, ok to final
ELE04-03888 Electrical Rough-In6/24/20056/24/20056/24/2005 3:26:32 PMPPASS
dan cell ; Phone #: ###-#### Internet Inspection Request from: Marsha Smylie south end of bldg, west wall only ok to cover
ELE05-02268 Rough-In Permanent Service6/24/20056/24/20056/24/2005 2:31:40 PMPPASS
ron ###-#### ric ok, p/s u/g n ok
ELE05-01745 Rough-In Permanent Service6/24/20056/24/20056/24/2005 1:46:48 PMPFAIL
Scheduled by a contractor via Hello! on 6/24/2005 at 8:29:07 AM. Contact: ###-####. called contr, left corr notice,250.32(b)(1)gnded cndr shall not be connected to gnd at sub-panel, 408.38 panels shall be dead-front, 110.26(2) width of work space shall be 30"
ELE05-02123 Electrical Rough-In6/24/20056/24/20056/24/2005 12:26:18 PMPPASS
bonding on swimming pool Internet Inspection Request from: Andy Rose ok to pour for pool deck only
ELE05-02044 Final6/23/20056/24/20056/24/2005 11:45:46 AMAPASS
one time inspection for installation of security lighting installed on south end of building. Questions call Delbert @ ###-#### Thank you. ; Phone #: ###-#### Internet Inspection Request from: BRIAN KEITH ok to final
ELE05-02060 Electrical Rough-In6/23/20056/24/20056/24/2005 10:05:56 AMACANC
john; Phone #: ###-#### Internet Inspection Request from: Barbara Moore did 6-23-05
ELE05-00393 Final6/23/20056/24/20056/24/2005 9:57:59 AMAPASS
brandon; Phone #: ###-#### Internet Inspection Request from: Letitia Mesa ok to final, signed occ card
ELE05-01536 Final6/23/20056/24/20056/24/2005 8:58:05 AMAFAIL
brandon; Phone #: ###-#### Internet Inspection Request from: Cathy Chiles only fixed gfci, not fixture. re-inspection fee due
ELE05-02251 Rough-In Permanent Service6/23/20056/24/20056/24/2005 8:37:08 AMAPASS
dino-- ###-#### ric ok, p/s u/g n ok
ELE05-02250 Rough-In Permanent Service6/23/20056/24/20056/24/2005 8:36:10 AMAPASS
dino-- ###-#### ric ok p/s u/g n ok
ELE05-02123 Electrical Rough-In6/23/20056/24/20056/24/2005 8:35:36 AMANH
Grid bonding inspection for swimming pool.; Phone #: ###-#### Internet Inspection Request from: Andy Rose called contr, no access, will recall
ELE05-01620 Final6/23/20056/24/20056/24/2005 8:34:33 AMAFAIL
brandon; Phone #: ###-#### Internet Inspection Request from: Cathy Chiles called left message,210.8.(A)(7) utility sink recpt shall have gfci if within 6', 314.21 drywall shall be repaired in entry way foe recpt, 314.25 cover shall be provided for box at range hood, left corr notice.