Inspections for the day of: Friday, June 24, 2005.
Number of inspections: 9
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorForrest France
TitleFIRE INSPECTOR
Phone #794-1981
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
BLD04-02157 BLD-Aging Inspection6/24/20056/24/20056/29/2005 10:22:35 AMPDONE
Stopped by and spoke with the store manager on 6/27/05 pm about this aging permit. He is to contact Mike Williams who will schedule an inspection.
FIR04-00531 INSP-Sprinkler Rough-in6/23/20056/24/20056/24/2005 3:12:15 PMPPART
Overhead main piping is good for cover except at trapeze nw side sheet fp2 where retaining strap is not attatched and at three locations where 4" main passes through block wall without proper seismic clearance. Also, exposed branch lines on roof must meet req. of NFPA 13 8.15.3.2.3.
FIR05-00340 INSP-Sprinkler Rough-in/Hydro6/23/20056/24/20056/24/2005 11:19:19 AMAPART
Overhead rough-in is good for cover. Area directly above door exiting west from TI space hallway lacks proper upright sprinkler coverage due to full height wall and adjacent beam.
BLD05-01093 FIRE-Final Inspection6/23/20056/24/20056/24/2005 10:04:51 AMACANC
This project has no fire inspection signatures required. Contacted Steven at ###-#### and told him to schedule for a structural inspection.
BLD05-01518 FIRE-Conference6/23/20056/24/20056/24/2005 9:37:31 AMADONE
On site discussion with Gill regarding his questions on fire sprinkler coverage as affected by the addition of two new office spaces.
FIR04-00258 INSP-Sprinkler Rough-in/Hydro6/21/20056/24/20056/24/2005 9:09:20 AMACANC
Cancel inspection per Jim Danes with De Best fire, they will re-schedule for next week.
FIR05-00253 INSP-Final Inspection6/23/20056/24/20056/24/2005 8:29:06 AMPCANC
This is Grants cell; Phone #: ###-#### Internet Inspection Request from: Terry Owsley Inspection cancelled from web by: Terry Owsley
FIR05-00252 INSP-Final Inspection6/23/20056/24/20056/24/2005 8:28:43 AMPCANC
Phone #: ###-#### Internet Inspection Request from: Terry Owsley Inspection cancelled from web by: Terry Owsley
FIR03-00091 FIR-Aging Inspection6/24/20056/24/20056/24/2005 12:00:00 AMPPASS
Permit finaled. The named tenant Corprate Express has moved.