BLD04-02157
| BLD-Aging Inspection | 6/24/2005 | 6/24/2005 | 6/29/2005 10:22:35 AM | P | DONE |
|
|
Stopped by and spoke with the store manager on 6/27/05 pm about this aging permit. He is to contact Mike Williams who will schedule an inspection.
|
FIR04-00531
| INSP-Sprinkler Rough-in | 6/23/2005 | 6/24/2005 | 6/24/2005 3:12:15 PM | P | PART |
|
|
Overhead main piping is good for cover except at trapeze nw side sheet fp2 where retaining strap is not attatched and at three locations where 4" main passes through block wall without proper seismic clearance. Also, exposed branch lines on roof must meet req. of NFPA 13 8.15.3.2.3.
|
FIR05-00340
| INSP-Sprinkler Rough-in/Hydro | 6/23/2005 | 6/24/2005 | 6/24/2005 11:19:19 AM | A | PART |
|
|
Overhead rough-in is good for cover. Area directly above door exiting west from TI space hallway lacks proper upright sprinkler coverage due to full height wall and adjacent beam.
|
BLD05-01093
| FIRE-Final Inspection | 6/23/2005 | 6/24/2005 | 6/24/2005 10:04:51 AM | A | CANC |
|
|
This project has no fire inspection signatures required. Contacted Steven at ###-#### and told him to schedule for a structural inspection.
|
BLD05-01518
| FIRE-Conference | 6/23/2005 | 6/24/2005 | 6/24/2005 9:37:31 AM | A | DONE |
|
|
On site discussion with Gill regarding his questions on fire sprinkler coverage as affected by the addition of two new office spaces.
|
FIR04-00258
| INSP-Sprinkler Rough-in/Hydro | 6/21/2005 | 6/24/2005 | 6/24/2005 9:09:20 AM | A | CANC |
|
|
Cancel inspection per Jim Danes with De Best fire, they will re-schedule for next week.
|
FIR05-00253
| INSP-Final Inspection | 6/23/2005 | 6/24/2005 | 6/24/2005 8:29:06 AM | P | CANC |
|
|
This is Grants cell; Phone #: ###-#### Internet Inspection Request from: Terry Owsley Inspection cancelled from web by: Terry Owsley
|
FIR05-00252
| INSP-Final Inspection | 6/23/2005 | 6/24/2005 | 6/24/2005 8:28:43 AM | P | CANC |
|
|
Phone #: ###-#### Internet Inspection Request from: Terry Owsley Inspection cancelled from web by: Terry Owsley
|
FIR03-00091
| FIR-Aging Inspection | 6/24/2005 | 6/24/2005 | 6/24/2005 12:00:00 AM | P | PASS |
|
|
Permit finaled. The named tenant Corprate Express has moved.
|