Inspections for the day of: Tuesday, June 24, 2008.
Number of inspections: 11
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorForrest France
TitleFIRE INSPECTOR
Phone #794-1981
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
FIR08-00392 INSP-Sprinkler Rough-in6/24/20086/24/20086/24/2008 9:36:14 PMPFAIL
Provide stock of QR sprinklers at the riser head boxes, one office as annotated on plans needs to be replaced with a quick response head, one missing escutcheon installed while on site, four added heads okayed.
FIR07-00997 INSP-Final Inspection6/24/20086/24/20086/24/2008 9:32:05 PMPPASS
Correction notice items verified for completion, OH fire sprinkler permit finaled.
FIR06-00292 INSP-Final Inspection6/24/20086/24/20086/24/2008 9:30:02 PMPPASS
Fire sprinkler permit finaled.
FIR08-00393 INSP-Final Inspection6/24/20086/24/20086/24/2008 2:34:42 PMPPART
OH rough-in for tenant related fire sprinkler system modifications are good for cover at the drop ceilings throughout.
FIR08-00418 INSP-Sprinkler Rough-in/Hydro6/24/20086/24/20086/24/2008 2:33:13 PMPFAIL
See plans for marked defficient areas including overspaced pendent heads at the south stairway, one missing hanger, also noted sidewinder sammy screws must be installed per mfg. listing (see plan hanger detail) and cannot be fastened to the narrow demention of the truss cord-eight locations.
FIR08-00343 INSP-Sprinkler Rough-in6/23/20086/24/20086/24/2008 1:25:08 PMADONE
OK to cover. KR
FIR08-00344 INSP-Sprinkler Rough-in6/23/20086/24/20086/24/2008 1:24:29 PMADONE
OK to cover. KR
FIR08-00066 INSP-Sprinkler Rough-in6/23/20086/24/20086/24/2008 11:19:13 AMAPART
Overhead rough-in is okay for cover at the drop ceilings, verified corrections, one head at the OTS mech. room east side remains to be relocated.
FIR08-00412 INSP-Final Inspection6/20/20086/24/20086/24/2008 10:59:43 AMAPASS
Fire sprinkler permit work finaled, minor field modification accepted.
FIR06-00917 INSP-Final Inspection6/19/20086/24/20086/24/2008 10:02:21 AMAPASS
Fire alarm testing completed satisfactory, permit finaled.
BLD08-01265 FIRE-Final Inspection6/23/20086/24/20086/24/2008 10:01:30 AMAFAIL
Project is not in condition for final life safety at this time, construction underway, missing exit signs and emergency lights, approved door hardware is not installed, walls and doors missing at some locations, fire extinguisher to be no higher than 48" AFF, discussed general project requirements with contractor.