Inspections for the day of: Thursday, June 24, 2010.
Number of inspections: 20
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorForrest France
TitleFIRE INSPECTOR
Phone #794-1981
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
BLD10-00778 FIRE-Final Inspection6/24/20106/24/20106/25/2010 4:52:21 PMPCANC
Overbooked
FIR10-00268 INSP-Final Inspection6/21/20106/24/20106/25/2010 12:50:55 PMAPASS
Fire sprinkler permit work passed site inspection.
FIR04-00655 INSP-Final Inspection6/23/20106/24/20106/25/2010 12:49:35 PMAFAIL
Re-inspection for correction items dated 2/7/05. Items still not repaired include; provide high/low air pressure switch monitoring, map at the FACP, signage at the riser door, battery trouble did not report. Items retested okay include sprinkler waterflow and phone line 2. Noted one duct detector has been installed and NFPA 72 forms were on site.
BLD10-00678 FIRE-Final Inspection6/23/20106/24/20106/25/2010 10:09:53 AMPPASS
Larry ###-####
BLD10-01118 FIRE-Final Inspection6/24/20106/24/20106/25/2010 10:09:22 AMPPASS
Fire life safety completed satisfactory, inspection passed.
FIR10-00271 INSP-Final Inspection6/23/20106/24/20106/25/2010 10:08:24 AMPPASS
Fire alarm work passed field testing, permit finaled.
FIR10-00243 INSP-Final Inspection6/24/20106/24/20106/25/2010 10:07:20 AMPPASS
Fire sprinkler permit finaled.
FIR10-00216 INSP-Final Inspection6/24/20106/24/20106/24/2010 3:06:19 PMPCANC
Inspection requested from web by: Jeff Packham Phone #: ###-#### Inspection cancelled from web by: Jeff Packham
FIR10-00085 FIR-Aging Inspection6/24/20106/24/20106/24/2010 12:02:48 PM DONE
Work in progress, site construction underway.
FIR08-00767 FIR-Aging Inspection6/24/20106/24/20106/24/2010 12:01:40 PM PEND
Contractor to request site inspection for permit final.
FIR08-00764 FIR-Aging Inspection6/24/20106/24/20106/24/2010 11:59:28 AM PEND
Permit final pending compliance with NFPA 25 5.5.1. Contractor has been notified.
FIR08-00696 FIR-Aging Inspection6/24/20106/24/20106/24/2010 11:55:26 AM PEND
Need site inspection request for permit final by contractor after noted corrections have been finished- see permit activity notes.
BLD09-00323 FIRE-Final Inspection6/23/20106/24/20106/24/2010 11:50:35 AMAPASS
Verified knox box is installed as needed per most recent fire life safety inspection activity note.
BLD10-00509 FIRE-Final Inspection6/23/20106/24/20106/24/2010 11:43:37 AMAPASS
early as possible//Ray Phone #: ###-####
BLD10-00508 FIRE-Final Inspection6/23/20106/24/20106/24/2010 11:43:10 AMAPASS
early as possible//Ray Phone #: ###-#### NOTE: Smoke evac and fire sprinkler work in progress for tenant improvement permit underway.
BLD10-00507 FIRE-Final Inspection6/23/20106/24/20106/24/2010 11:37:19 AMAPASS
early as possible//Ray Phone #: ###-####
BLD10-00791 FIRE-Final Inspection6/23/20106/24/20106/24/2010 11:36:48 AMAFAIL
Missing fire extinguishers-need to post and provide with current tags, one exit sign is not functional, door hardware at the second exit is backward, missing tactile sign per plan notes, project is not in condition for final at this time, missing ceiling tile, etc.
FIR09-00713 INSP-Final Inspection6/22/20106/24/20106/24/2010 11:34:06 AMACANC
Scott Phone #: ###-#### Overbooked
FIR09-00712 INSP-Final Inspection6/22/20106/24/20106/24/2010 11:33:37 AMACANC
Overbooked
FIR10-00274 INSP-Final Inspection6/24/20106/24/20106/24/2010 11:33:08 AMADEFR
Contact: Rob Ahten - system has been tested, needs to be signed off Inspection requested from web by: Deb Gooden Phone #: ###-####