Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
FIR11-00219 INSP-Alarm Testing6/16/20116/17/2011 A 
Phone #: ###-#### >> Inspection requested via web by Robert Gobler
FIR11-00025 INSP-Final Inspection6/22/20116/22/2011 P 
Troy phone #: ###-####
FIR09-00429 FIR-Aging Inspection6/24/20116/24/20116/24/2011 4:33:24 PM DONE
FIR09-00443 FIR-Aging Inspection6/24/20116/24/20116/24/2011 4:33:07 PM DONE
BLD11-00993 FIRE-Final Inspection6/24/20116/24/20116/24/2011 4:32:23 PMPPASS
Fire life safety passed. Scope of work completed.
FIR11-00262 INSP-Sprinkler Rough-in6/24/20116/24/20116/24/2011 4:31:40 PMPPART
Rough-in passed with the exception of three areas as noted on approved plans including one head blocked by an adjacent column, noted overspaced heads outside the remodel area due to new tenant demising wall, two concealed spaces need sprinkler protection or must meet allowable exceptions. Existing system must have a current annual inspection prior to final.
FIR11-00264 INSP-Final Inspection6/23/20116/24/20116/24/2011 4:27:21 PMAPASS
Fire sprinkler permit finaled.
FIR11-00293 INSP-Sprinkler Rough-in6/23/20116/24/20116/24/2011 4:26:43 PMAPART
Overhead fire sprinkler system modifications at the tenant remodel are approved for cover. One high temp. head at the group meeting room needs replaced with an ordinary temp. rated head to match the remainder of sprinklers in the compartment per NFPA 13 8.3.2.1.
FIR11-00212 INSP-Sprinkler Rough-in6/23/20116/24/20116/24/2011 4:20:03 PMAPART
Added upright sprinklers at the east end open office area soffit (due to ductwork obstructions) as marked and dated on approved plans okay for cover.