FIR11-00219
| INSP-Alarm Testing | 6/16/2011 | 6/17/2011 | | A | |
|
|
Phone #: ###-#### >> Inspection requested via web by Robert Gobler
|
FIR11-00025
| INSP-Final Inspection | 6/22/2011 | 6/22/2011 | | P | |
|
|
Troy phone #: ###-####
|
FIR09-00429
| FIR-Aging Inspection | 6/24/2011 | 6/24/2011 | 6/24/2011 4:33:24 PM | | DONE |
|
|
|
FIR09-00443
| FIR-Aging Inspection | 6/24/2011 | 6/24/2011 | 6/24/2011 4:33:07 PM | | DONE |
|
|
|
BLD11-00993
| FIRE-Final Inspection | 6/24/2011 | 6/24/2011 | 6/24/2011 4:32:23 PM | P | PASS |
|
|
Fire life safety passed. Scope of work completed.
|
FIR11-00262
| INSP-Sprinkler Rough-in | 6/24/2011 | 6/24/2011 | 6/24/2011 4:31:40 PM | P | PART |
|
|
Rough-in passed with the exception of three areas as noted on approved plans including one head blocked by an adjacent column, noted overspaced heads outside the remodel area due to new tenant demising wall, two concealed spaces need sprinkler protection or must meet allowable exceptions. Existing system must have a current annual inspection prior to final.
|
FIR11-00264
| INSP-Final Inspection | 6/23/2011 | 6/24/2011 | 6/24/2011 4:27:21 PM | A | PASS |
|
|
Fire sprinkler permit finaled.
|
FIR11-00293
| INSP-Sprinkler Rough-in | 6/23/2011 | 6/24/2011 | 6/24/2011 4:26:43 PM | A | PART |
|
|
Overhead fire sprinkler system modifications at the tenant remodel are approved for cover. One high temp. head at the group meeting room needs replaced with an ordinary temp. rated head to match the remainder of sprinklers in the compartment per NFPA 13 8.3.2.1.
|
FIR11-00212
| INSP-Sprinkler Rough-in | 6/23/2011 | 6/24/2011 | 6/24/2011 4:20:03 PM | A | PART |
|
|
Added upright sprinklers at the east end open office area soffit (due to ductwork obstructions) as marked and dated on approved plans okay for cover.
|