GCE13-00107
| GCE-Rough-In | 6/24/2013 | 6/24/2013 | 6/25/2013 12:40:39 PM | P | PASS |
|
|
###-#### or ###-#### Unit locked. Called number given as contact and was informed that no one would be there today. Lighting retro rough in ok
|
ELE10-00317
| ELE-Aging Inspection | 6/24/2013 | 6/24/2013 | 6/24/2013 3:26:01 PM | | DONE |
|
|
Waiting on owner
|
GCE13-00108
| GCE-Rough-In | 6/24/2013 | 6/24/2013 | 6/24/2013 2:46:53 PM | P | FAIL |
|
|
John ###-#### 250.24(A)(1)- The grounding electode conductor shall connect to the same terminal or bus as the grounded conductor. 314.23(B)(1)- Screws where used as a fastening means shall not pass through box unless protected to avoid abrasion.
|
ELE13-01046
| Final | 6/24/2013 | 6/24/2013 | 6/24/2013 2:36:29 PM | P | PASS |
|
|
Phone #: ###-#### >> Inspection requested via web by John VanZandt Final ok
|
ELE13-00685
| Electrical Rough-In | 6/24/2013 | 6/24/2013 | 6/24/2013 1:53:43 PM | P | PASS |
|
|
potting inspection 1 light Phone #: ###-#### >> Inspection requested via web by mike brown Rough in ok cover
|
ELE13-01619
| Conference | 6/24/2013 | 6/24/2013 | 6/24/2013 1:17:58 PM | P | DONE |
|
|
need conference on electrical, please call Francis @ ###-#### or ###-####. would like to meet at site at 1:00 if possible. Phone #: ###-#### >> Inspection requested via web by Andy Rose Discussed existing wiring pulled through panel. New panel to unit and existing panel to be gutted and used as junction point.
|
ELE13-01614
| Permanent Service | 6/24/2013 | 6/24/2013 | 6/24/2013 12:50:07 PM | P | CANC |
|
|
Phone #: ###-#### >> Inspection requested via web by John VanZandt Requested by mistake, will correct address to east Jefferson
|
ELE13-00514
| Final | 6/23/2013 | 6/24/2013 | 6/24/2013 12:02:52 PM | A | FAIL |
|
|
Call Dene for access code Thank you Phone #: ###-#### >> Inspection requested via web by kim grundhauser 440.6, and 310.16- over current shall be sized per conductor installed
|
ESC13-00541
| Site Preparation | 6/24/2013 | 6/24/2013 | 6/24/2013 9:39:52 AM | | PASS |
|
|
Spoke to RP sign will be posted 6-24-13
|
ELE13-01586
| Temporary Service | 6/21/2013 | 6/24/2013 | 6/24/2013 9:17:50 AM | A | PASS |
|
|
As early as possible Phone #: 2089899410 >> Inspection requested via mobile web by john harvey t/s o/h n ok
|
GCE13-00106
| GCE-Rough-In Permanent Service | 6/21/2013 | 6/24/2013 | 6/24/2013 8:58:59 AM | A | PASS |
|
|
Terry ###-#### Rough in ok cover p/s u/g n ok
|
ELE13-01565
| Rough-In Permanent Service | 6/21/2013 | 6/24/2013 | 6/24/2013 8:57:52 AM | A | FAIL |
|
|
rough/ final tbd Phone #: ###-#### >> Inspection requested via web by Dave Koeppen 210.8 All 15 and 20 amp recepticals shall have GFCI protection
|