Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
BLD13-01113 FIRE-Sprinkler Rough-in6/24/20136/24/20136/24/2013 5:29:19 PMAPART
Okay to cover fire sprinkler modifications at the grid ceilings.
FIR12-00252 INSP-Final Inspection6/21/20136/24/20136/24/2013 5:27:32 PMPPART
Correction items verified for completion. Scope of work passed field testing. Final pending FIR12-00090 (ref. review notes and project description).
BLD13-00341 FIRE-Final Inspection6/24/20136/24/20136/24/2013 5:21:18 PMPFAIL
Painted fire sprinkler heads at five locations will need replaced. Ref. NFPA 13 2010 6.2.6.2.2.
BLD11-02317 FIRE-Final Inspection6/21/20136/24/20136/24/2013 5:12:21 PMPPART
Items on the previous correction list are finished with the exception of one junction box cover above the basement level fire panel and plan modification for project related FIR trade work.