Inspections for the day of: Tuesday, June 24, 2014.
Number of inspections: 19
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorRock A. Hudson
TitleELE-INSPECTOR
Phone #794-6794
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
ELE14-01657 Final6/23/20146/24/20146/24/2014 4:10:25 PMPPASS
Please call Mark at least 10 min. prior.
Homeowner is pulling permit for addition which is also ready for insp. Phone #: ###-#### >> Inspection requested via web by Mark Estep Wiring for smoke detectors final ok
ELE14-00051 Electrical Rough-In6/24/20146/24/20146/24/2014 4:05:08 PMPPASS
gracie Phone #: ###-#### Kitchen and master bedroom only rough in ok cover
ELE14-01665 Final6/24/20146/24/20146/24/2014 4:03:03 PMPPASS
Call ahead 10min - Mark Phone #: ###-#### Wall was added over 10 years ago without permits creating small room on back of garage. All receptical outlets wired correctly. Receptical outlet layout for habitable room ok. Sheath of NM cable enters box beyond minimal required. Final ok
ELE14-01629 Final6/24/20146/24/20146/24/2014 3:09:46 PMPPASS
Phone #: ###-#### >> Inspection requested via web by cory carman Final ok
ELE14-01644 Electrical Rough-In6/24/20146/24/20146/24/2014 2:31:25 PMPPASS
This will be a rough in inspection for the lighting retrofit we are doing. Please contact Dean Gernaat. He is on sight. Thank you and have a good day! Phone #: ###-#### >> Inspection requested via web by Laura Longshaw Check on final flexible cord removed on fixures in lobby south end. UL listing confirmed
ELE13-03054 Final6/24/20146/24/20146/24/2014 2:31:00 PMPPASS
Final ok
ELE14-00860 Electrical Rough-In6/24/20146/24/20146/24/2014 1:58:19 PMPPASS
banquet area ceiling Phone #: ###-#### >> Inspection requested via web by Lee VanSchoiack Rough in ok cover
ELE14-01661 Final6/24/20146/24/20146/24/2014 1:12:59 PMPFAIL
Contact: Derrick Kamper Phone #: ###-#### >> Inspection requested via web by Deb Gooden 250.52(B)(1)- Gas piping system shall not be ussed as grounding elctrode.
250.53(D)(2)- Under ground metal water pipe shall be suplemented by additional grounding electrode type specified in 250.52
ELE14-01654 Rough-In Permanent Service6/24/20146/24/20146/24/2014 12:43:59 PMPNR
Any questions please let me know, thx. TW. Phone #: ###-#### >> Inspection requested via web by Stephen Kren
ELE13-01476 Electrical Rough-In6/23/20146/24/20146/24/2014 12:04:37 PMAPASS
Cody Phone #: ###-#### Foyer under WPS sign walls and hard lid, 3 office wall rough in ok cover
ELE14-01612 Rough-In Permanent Service6/23/20146/24/20146/24/2014 11:16:13 AMAPASS
Corrections made Phone #: ###-#### >> Inspection requested via web by Lars Johnson Rough in ok cover p/s o/h rec ok
ELE14-01271 Electrical Rough-In6/23/20146/24/20146/24/2014 10:55:39 AMAPASS
Call for access Phone #: 6299948 >> Inspection requested via mobile web by David McClellan Rough in ok cover
ELE14-01271 Permanent Service6/24/20146/24/20146/24/2014 10:55:22 AMPPASS
Call for access Phone #: 6299948 >> Inspection requested via mobile web by David McClellan p/s u/g rec ok
ELE14-01295 Electrical Rough-In6/24/20146/24/20146/24/2014 10:32:30 AMAPASS
Need parking lot pole base inspection for three locations Phone #: ###-#### >> Inspection requested via web by Jerry Moore 3 pole bases rough in ok cover
ELE14-01359 Electrical Rough-In6/24/20146/24/20146/24/2014 10:20:21 AMAPASS
walls Phone #: ###-#### >> Inspection requested via web by Lee VanSchoiack Medical wall rough in ok cover
ELE14-01357 Electrical Rough-In6/24/20146/24/20146/24/2014 10:19:41 AMAPASS
ceiling Phone #: ###-#### >> Inspection requested via web by Lee VanSchoiack All ceilings ok except room 205 Rough in ok cover
ELE13-03054 Final6/23/20146/24/20146/24/2014 9:44:10 AMANH
steven Phone #: ###-#### No access due to key missing
GCE14-00014 GCE-Final6/23/20146/24/20146/24/2014 9:02:01 AMAPASS
David ###-#### Final ok
ELE13-03105 Electrical Rough-In6/23/20146/24/20146/24/2014 8:41:00 AMAPASS
pipe and boxes in wall 27 Phone #: ###-#### >> Inspection requested via web by matt miller North 3rd of wall 27 pour rough in ok cover