ELE13-01035
| ELE-Aging Inspection | 6/24/2015 | 6/24/2015 | 6/25/2015 7:44:21 AM | | DONE |
|
|
too busy
|
ELE15-01872
| Rough-In Permanent Service | 6/23/2015 | 6/24/2015 | 6/24/2015 3:02:13 PM | P | PASS |
|
|
extended service conductors in to home j-box on west side just passed backdoor under home Phone #: ###-#### Inspection requested via web by Thomas wilson r/i ok p/s u/g rec ok
|
ELE15-01904
| Rough-In Permanent Service | 6/24/2015 | 6/24/2015 | 6/24/2015 2:13:22 PM | P | FAIL |
|
|
Phone #: ###-#### Inspection requested via web by steve cooper 210.52(D)-in dwelling units at least one receptacle shall be installed in bathrooms within 3 foot of each basin. 300.4-not less than 11/4" from bored holes to edge of stud.
|
ELE13-03438
| Permanent Service | 6/24/2015 | 6/24/2015 | 6/24/2015 1:36:12 PM | P | CANC |
|
|
Please contact Jeremiah Goins on site at ###-#### Phone #: ###-#### Inspection requested via web by Deb Gooden needed r/i for performance test completion
|
ELE13-03438
| Electrical Rough-In | 6/24/2015 | 6/24/2015 | 6/24/2015 1:35:52 PM | P | PASS |
|
|
Please contact Jeremiah Goins on site at ###-#### Phone #: ###-#### Inspection requested via web by Deb Gooden performance test completed (p/s already passed)
|
ELE13-03438
| Electrical Rough-In | 6/24/2015 | 6/24/2015 | 6/24/2015 1:34:13 PM | P | PASS |
|
|
Please contact Jeremiah Goins on site at ###-#### Phone #: ###-#### Inspection requested via web by Deb Gooden performance test completed
|
GCE15-00097
| GCE-Rough-In | 6/24/2015 | 6/24/2015 | 6/24/2015 12:44:26 PM | P | PASS |
|
|
Shawn ###-#### - underground and grounding for shop/garage 2" pvc in slab and ground rods r/i ok
|
GCE15-00098
| GCE-Rough-In | 6/24/2015 | 6/24/2015 | 6/24/2015 12:43:30 PM | P | PASS |
|
|
Shawn ###-#### - underground and grounding for shop/garage r/i ok 2" pvc in slab and ground rods
|
ELE15-01472
| Electrical Rough-In | 6/23/2015 | 6/24/2015 | 6/24/2015 11:10:30 AM | A | PASS |
|
|
Please provide us with a ceiling inspection. Joel Hudson Phone #: ###-#### Inspection requested via web by Kevin Perez r/i t bar ceilings ok to cover
|
ELE15-00956
| Final | 6/23/2015 | 6/24/2015 | 6/24/2015 10:54:33 AM | A | PASS |
|
|
Shane is the contact his cell no. is ###-#### Phone #: ###-#### Inspection requested via web by Shawna Gates final ok
|
GCE15-00067
| GCE-Final | 6/23/2015 | 6/24/2015 | 6/24/2015 10:10:49 AM | A | FAIL |
|
|
Ben ###-#### 110.24(A)- fault current needs date also. Exterior light pole or sign bases not poured and no wire installed in raceways??
|
GCE14-00207
| GCE-Permanent Service | 6/23/2015 | 6/24/2015 | 6/24/2015 9:27:54 AM | A | PASS |
|
|
Kevin ###-#### - service insp. p/s u/g n ok
|
ELE14-02710
| Final | 6/23/2015 | 6/24/2015 | 6/24/2015 8:25:58 AM | A | PASS |
|
|
Phone #: ###-#### Inspection requested via web by Thomas Jenkins final ok
|