FIR16-00261
| INSP-Final Inspection | 6/22/2016 | 6/24/2016 | 6/24/2016 3:40:19 PM | P | PASS |
|
|
Fire alarm inspection for level 1 passed/complete.
|
FIR16-00311
| INSP-Sprinkler Rough-in/Hydro | 6/24/2016 | 6/24/2016 | 6/24/2016 2:28:21 PM | P | PASS |
|
|
Rough to cover inspection for overhead fire sprinkler piping complete, overhead fire sprinkler approved for cover.
|
BLD16-02231
| FIRE-Final Inspection | 6/24/2016 | 6/24/2016 | 6/24/2016 12:14:58 PM | P | PASS |
|
|
No fire sprinkler modifications, no fire alarm modifications, fire extinguisher is in place and will tagged with current inspection tag. Final life fire safety inspection passed/complete.
|
BLD16-02244
| FIRE-Final Inspection | 6/24/2016 | 6/24/2016 | 6/24/2016 11:55:58 AM | P | PASS |
|
|
No fire sprinklers , no fire alarms, fire extinguisher is in place and will get an inspection tag. Final life fire safety inspection passed/complete.
|
BLD16-02232
| FIRE-Final Inspection | 6/24/2016 | 6/24/2016 | 6/24/2016 11:41:31 AM | P | PASS |
|
|
No fire sprinkler, no fire alarms, discussed location to mount fire extinguisher when painting is finished. Final life fire safety inspection passed/complete.
|
BLD16-02233
| FIRE-Final Inspection | 6/24/2016 | 6/24/2016 | 6/24/2016 11:18:22 AM | P | FAIL |
|
|
Fire sprinklers overspaced in front of showroom area, heads to close together in the rear storage area. Exit sign located by front entry needs to be serviced, exit light is currently inoperable.
|
FIR16-00404
| INSP-Sprinkler Rough-in/Hydro | 6/24/2016 | 6/24/2016 | 6/24/2016 10:45:41 AM | P | PART |
|
|
Rough to cover inspection for overhead fire sprinklers in the main entry hardlid, fire sprinkler piping above main entry hardlid approved for cover.
|
FIR16-00214
| INSP-Final Inspection | 6/22/2016 | 6/24/2016 | 6/24/2016 10:26:26 AM | A | PASS |
|
|
Final fire sprinkler inspection passed/complete.
|
FIR16-00146
| INSP-Sprinkler Rough-in/Hydro | 6/23/2016 | 6/24/2016 | 6/24/2016 9:52:29 AM | A | PASS |
|
|
Hydrostatic test for overhead fire sprinkler piping complete for level 5.
|
BLD16-01501
| FIRE-Conference | 6/23/2016 | 6/24/2016 | 6/24/2016 9:32:39 AM | A | DONE |
|
|
Fire conference complete, discussed area's that would be acceptable to cover with ceiling tile.
|
BLD16-02291
| FIRE-Final Inspection | 6/23/2016 | 6/24/2016 | 6/24/2016 9:07:48 AM | A | PASS |
|
|
No fire sprinkler modifications, no fire alarm modifications, fire extinguishers are in place with current inspection tags. Final life fire safety inspection passed/complete.
|
FIR14-00870
| INSP-Final Inspection | 6/21/2016 | 6/24/2016 | 6/24/2016 8:46:37 AM | A | PASS |
|
|
Final fire alarm inspection passed/complete
|