Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
ELE20-01657 Electrical Rough-In6/24/20206/24/20206/24/2020 2:13:39 PMPPASS
Phone #: ###-#### Inspection requested via web by Casey Fouts Informed any form of cover is not allowed. no one siding, no grid boarders. One siding started. Wall rough in ok cover
ELE20-02141 Electrical Rough-In6/23/20206/24/20206/24/2020 1:43:59 PMPPASS
Contact: Andy Eckhart. underground inspection please Phone #: ###-#### Inspection requested via web by Deb Gooden Under footing conduits rough in ok cover
ELE20-02079 Permanent Service6/24/20206/24/20206/24/2020 1:20:55 PMPPASS
Service inspection for historic street lights meter pedestal. Danny is the contact. Phone #: ###-#### Inspection requested via web by Buster Bowen
Located at northeast corner of building. p/s u/g n ok
ELE20-01626 Electrical Rough-In6/24/20206/24/20206/24/2020 12:31:42 PMPPASS
Soffit off of garage has a recessed can light. Thank you Phone #: ###-#### Inspection requested via web by Eric Brown Can in soffit in front of small garage door rough in ok cover.
ELE20-01939 Rough-In Permanent Service6/22/20206/24/20206/24/2020 11:21:21 AMACANC
Phone #: ###-#### Inspection requested via web by Trevor Soesbe Service only at this time.
ELE20-01939 Permanent Service6/24/20206/24/20206/24/2020 10:48:50 AMPPASS
Phone #: ###-#### Inspection requested via web by Trevor Soesbe At time of inspection no BLD found with search, new windows and siding. Service only at this time. p/s o/h rec ok
ELE19-04107 Final6/23/20206/24/20206/24/2020 10:26:12 AMAFAIL
garage code 4224 Phone #: ###-#### Inspection requested via web by Troy Ballard 110.26-Minimum work space shall be provided for meter base. Mini-split positioned directly in front of meter.
ELE19-04799 Conference6/23/20206/24/20206/24/2020 9:58:25 AMAPASS
Conference to discuss the connection of the fire pump Phone #: ###-#### Inspection requested via web by Jason Parke Discussed supply conductors and equipment on supply side of fire pump service. Service entrance conductor travel underground from Idaho power vault to a CT can then to fire pump controller. CT can shown on wall out of fire pump room. Explained supply side conductors shall be installed as service entrance conductors and shall be physically outside building or installed as per 230.6 concidered outside the building as per 695.6(A)(1). CT can will be required to be located in same room as fire pump for fire protection or relocate CT meter to transformer with service entrance to directly enter fire pump service disconnecting means.
ELE20-01657 Electrical Rough-In6/24/20206/24/20206/24/2020 9:32:27 AMANR
Please call in advance to ensure access. Rough in for cover. Phone #: ###-#### Inspection requested via web by Casey Fouts
Contractor asked to reschedule
ELE20-02038 Temporary Service6/23/20206/24/20206/24/2020 9:29:38 AMACANC
Phone #: ###-#### >> Inspection requested via web by Alan Lusk Inspection cancelled from web by: Alan Lusk
ELE20-01102 Electrical Rough-In6/23/20206/24/20206/24/2020 9:02:22 AMAPASS
Overhead inspection please. Thank you. Phone #: ###-#### Inspection requested via web by Kyle Lott Grid rough in ok cover