ELE20-01657
| Electrical Rough-In | 6/24/2020 | 6/24/2020 | 6/24/2020 2:13:39 PM | P | PASS |
|
|
Phone #: ###-#### Inspection requested via web by Casey Fouts Informed any form of cover is not allowed. no one siding, no grid boarders. One siding started. Wall rough in ok cover
|
ELE20-02141
| Electrical Rough-In | 6/23/2020 | 6/24/2020 | 6/24/2020 1:43:59 PM | P | PASS |
|
|
Contact: Andy Eckhart. underground inspection please Phone #: ###-#### Inspection requested via web by Deb Gooden Under footing conduits rough in ok cover
|
ELE20-02079
| Permanent Service | 6/24/2020 | 6/24/2020 | 6/24/2020 1:20:55 PM | P | PASS |
|
|
Service inspection for historic street lights meter pedestal. Danny is the contact. Phone #: ###-#### Inspection requested via web by Buster Bowen Located at northeast corner of building. p/s u/g n ok
|
ELE20-01626
| Electrical Rough-In | 6/24/2020 | 6/24/2020 | 6/24/2020 12:31:42 PM | P | PASS |
|
|
Soffit off of garage has a recessed can light. Thank you Phone #: ###-#### Inspection requested via web by Eric Brown Can in soffit in front of small garage door rough in ok cover.
|
ELE20-01939
| Rough-In Permanent Service | 6/22/2020 | 6/24/2020 | 6/24/2020 11:21:21 AM | A | CANC |
|
|
Phone #: ###-#### Inspection requested via web by Trevor Soesbe Service only at this time.
|
ELE20-01939
| Permanent Service | 6/24/2020 | 6/24/2020 | 6/24/2020 10:48:50 AM | P | PASS |
|
|
Phone #: ###-#### Inspection requested via web by Trevor Soesbe At time of inspection no BLD found with search, new windows and siding. Service only at this time. p/s o/h rec ok
|
ELE19-04107
| Final | 6/23/2020 | 6/24/2020 | 6/24/2020 10:26:12 AM | A | FAIL |
|
|
garage code 4224 Phone #: ###-#### Inspection requested via web by Troy Ballard 110.26-Minimum work space shall be provided for meter base. Mini-split positioned directly in front of meter.
|
ELE19-04799
| Conference | 6/23/2020 | 6/24/2020 | 6/24/2020 9:58:25 AM | A | PASS |
|
|
Conference to discuss the connection of the fire pump Phone #: ###-#### Inspection requested via web by Jason Parke Discussed supply conductors and equipment on supply side of fire pump service. Service entrance conductor travel underground from Idaho power vault to a CT can then to fire pump controller. CT can shown on wall out of fire pump room. Explained supply side conductors shall be installed as service entrance conductors and shall be physically outside building or installed as per 230.6 concidered outside the building as per 695.6(A)(1). CT can will be required to be located in same room as fire pump for fire protection or relocate CT meter to transformer with service entrance to directly enter fire pump service disconnecting means.
|
ELE20-01657
| Electrical Rough-In | 6/24/2020 | 6/24/2020 | 6/24/2020 9:32:27 AM | A | NR |
|
|
Please call in advance to ensure access. Rough in for cover. Phone #: ###-#### Inspection requested via web by Casey Fouts Contractor asked to reschedule
|
ELE20-02038
| Temporary Service | 6/23/2020 | 6/24/2020 | 6/24/2020 9:29:38 AM | A | CANC |
|
|
Phone #: ###-#### >> Inspection requested via web by Alan Lusk Inspection cancelled from web by: Alan Lusk
|
ELE20-01102
| Electrical Rough-In | 6/23/2020 | 6/24/2020 | 6/24/2020 9:02:22 AM | A | PASS |
|
|
Overhead inspection please. Thank you. Phone #: ###-#### Inspection requested via web by Kyle Lott Grid rough in ok cover
|