Inspections for the day of: Tuesday, June 25, 2002.
Number of inspections: 11
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorJack Frank
TitleELE-INSPECTOR
Phone #794-1930
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
ELE02-01923 Electrical Rough-In6/24/20026/25/20026/25/2002 12:00:00 AMAPART
###-#### BRUCE bathrm only, note old house turned into chiropractic office 6/25/2002 10:30:31 AM
ELE02-01926 Electrical Rough-In6/24/20026/25/20026/25/2002 12:00:00 AMAPART
PAT ###-#### r/i ok 6/25/2002 1:18:55 PM
ELE02-01925 Temporary Service6/24/20026/25/20026/25/2002 12:00:00 AMAFAIL
AL ###-#### cor. posted talked with contractor at job site 110.14(A) ringed wires,200.6 shall not ID 6or smaller250.8 no SMS, 250.24 terminate grd at nuetral bus ,install bond screw, 250.70 110.3(B) terminate each grd wire under it's grd clamp 6/25/2002 11:45:04 AM
ELE02-01863 Temporary Service6/24/20026/25/20026/25/2002 12:00:00 AMAPASS
t/p--- cory ###-####


t/s u/g new ok 6/24/2002 5:50:53 PM
ELE02-01915 Final6/24/20026/25/20026/25/2002 12:00:00 AMACANC
marv- ###-#### fn called wrong address, and no access need to meet contractor for access 6/25/2002 10:57:47 AM
ELE00-04435 Electrical Rough-In6/24/20026/25/20026/25/2002 12:00:00 AMPPART
###-#### Bob Johnson conference ok cow 6/25/2002 5:09:52 PM
ELE02-01447 Final6/24/20026/25/20026/25/2002 12:00:00 AMPNR
Scheduled by a contractor via Hello! on 06/24/2002 at 17:05:47. Contact: ###-####. called needs shelves install both walkin closets 6/25/2002 5:48:57 PM
ELE02-01290 Electrical Rough-In6/25/20026/25/20026/25/2002 12:00:00 AMPFAIL
DAVID ###-#### cor. posted talked with owner 110.3(B)&110.14 use listed tool for crimp sleeves and 314.20 outside boxes not flush, 300.4, 300.14 6 inches free lenght 6/25/2002 5:09:10 PM
ELE02-01905 Electrical Rough-In6/25/20026/25/20026/25/2002 12:00:00 AMPPART
MIKE ###-#### ok 6/25/2002 2:46:05 PM
ELE02-01911 Electrical Rough-In6/25/20026/25/20026/25/2002 12:00:00 AMPPART
MIKE ###-####ok 6/25/2002 2:46:14 PM
ELE02-01932 Rough-In Permanent Service6/25/20026/25/20026/25/2002 12:00:00 AMPFAIL
###-#### jim cor. posted called 300.4 314.20 out boxes 6/25/2002 5:31:33 PM