Inspections for the day of: Tuesday, June 25, 2002.
Number of inspections: 9
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorRick Jackson
TitleFIRE INSPECTOR
Phone #794-1981
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
BLD02-00759 FIRE-Final Inspection6/24/20026/25/20026/25/2002 12:00:00 AMAFAIL
###-#### LISA CALL 1ST need smoke detector within 5 feet of door on hold open 6/25/2002 2:00:22 PM
MIS01-00172 FIR-Final6/24/20026/25/20026/25/2002 12:00:00 AMAPASS
###-####
BLD01-02531 FIRE-Final Inspection6/24/20026/25/20026/25/2002 12:00:00 AMAFAIL
###-#### penetrations and combustibles above grid ceiling on first floor; second floor has penetrations 6/25/2002 10:00:50 AM
BLD99-01404 FIRE-Final Inspection6/24/20026/25/20026/25/2002 12:00:00 AMAPASS
###-####
BLD01-02828 FIRE-Sprinkler Rough-in6/24/20026/25/20026/25/2002 12:00:00 AMAFAIL
JIM- ###-#### R/I insulation needs to be stapled to joist or secured 6/25/2002 8:26:12 AM
BLD02-00731 FIRE-Conference6/24/20026/25/20026/25/2002 12:00:00 AMAPART
###-#### exit signs to installed as redlined on approved plans 6/25/2002 8:01:34 AM
BLD02-00296 FIRE-Final Inspection6/24/20026/25/20026/25/2002 12:00:00 AMAPASS
Scheduled by a contractor via Hello! on 06/24/2002 at 14:01:21. Contact: ###-####.
FIR02-00130 INSP-Sprinkler Rough-in/Hydro6/24/20026/25/20026/25/2002 12:00:00 AMPFAIL
Scheduled by a contractor via Hello! on 06/24/2002 at 14:54:55. Contact: ###-####. eq on main feed and FDC; need walls at AHU in basement 6/25/2002 4:33:54 PM
MIS02-00125 FIR-Final6/25/20026/25/20026/25/2002 12:00:00 AMPPASS
gail ###-#### call 1st before insp--