Inspections for the day of: Monday, June 25, 2007.
Number of inspections: 12
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorBob Reichert
TitleELE-INSPECTOR
Phone #794-1923
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
ELE07-02268 Electrical Rough-In6/25/20076/25/20076/25/2007 4:01:02 PMPPASS
contact: John Ostolasa Phone #: ###-#### Internet Inspection Request from: Deb Gooden new walls only ok to cover
ELE07-02266 Electrical Rough-In6/25/20076/25/20076/25/2007 3:33:44 PMPPASS
garage door will be open Phone #: ###-#### Internet Inspection Request from: Jarrod Clymer called contr , ric ok
ELE07-02237 Electrical Rough-In6/25/20076/25/20076/25/2007 2:58:06 PMPFAIL
jack Phone #: ###-#### called, left corr notice, nec 300.4(A)&(D) edge of bored holes and nm cable shall be 1 1/4" from edge of framing members, 210.52(A)(1) outlets shall be spaced such that no point along wall line is over 6' from an outlet,210.52(H)hallways over 10' shall have an outlet, 210.52(E) there shall be an outlet at front and rear of dwelling, 110.26(F)(1)(b) there shall be no ducts in dedicated space over panel BCC no violations shall be retained,nm cable shall run thru holes in studs, framing shall be done for inspection
ELE07-01321 Electrical Rough-In6/22/20076/25/20076/25/2007 2:12:44 PMPPART
matt - grid; Phone #: ###-#### Internet Inspection Request from: Victoria Apatang east 1/2 2nd floor ceiling only ok to cover
ELE07-02173 Permanent Service6/25/20076/25/20076/25/2007 1:42:54 PMPPASS
randy Phone #: ###-#### corrections made, p/s o/h rec ok
ELE07-02245 Electrical Rough-In6/25/20076/25/20076/25/2007 12:41:59 PMPPASS
Upher Phone #: ###-#### Internet Inspection Request from: Kerri Hamilton ok to pour concrete encased electrode
ELE07-01482 Permanent Service6/25/20076/25/20076/25/2007 12:19:28 PMPPASS
robert Phone #: ###-#### corr made, p/s u/g n ok
ELE07-00933 Final6/25/20076/25/20076/25/2007 10:02:56 AMAPASS
looked at sign, ok to final
ELE07-00666 Final6/25/20076/25/20076/25/2007 10:00:04 AMAPASS
looked at sign, ok to final
ELE06-00182 Final6/22/20076/25/20076/25/2007 9:33:31 AMAPASS
Phone #: ###-#### Internet Inspection Request from: Alan Lusk called contr to add bkr closure plate, ok to final
ELE07-01633 Final6/22/20076/25/20076/25/2007 8:48:54 AMAPASS
jay; Phone #: ###-#### Internet Inspection Request from: Victoria Apatang ok to final
ELE07-02249 Temporary Service6/22/20076/25/20076/25/2007 8:10:44 AMAPASS
Joe Phone #: ###-#### Internet Inspection Request from: Joseph Zumwalt t/s u/g n ok