Inspections for the day of: Monday, June 25, 2007.
Number of inspections: 18
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorForrest France
TitleFIRE INSPECTOR
Phone #794-1981
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
MIS07-00141 FIR-Final6/25/20076/25/20076/25/2007 5:04:17 PMPFAIL
Met contact on site who could not provide access to the building due to missing keys, no inspection completed.
BLD07-00665 FIRE-Final Inspection6/22/20076/25/20076/25/2007 4:56:50 PMAFAIL
Need to repair one emergency light at the main lobby, remove manual thumbturn at the office door, post the provided 2A10BC fire extinguisher on the wall as discussed, need to final the project related fire alarm permit prior to life safety final, noted slider doors at three private dining rooms may not meet hardware accessibility requirements as installed.
FIR07-00541 INSP-Final Inspection6/22/20076/25/20076/25/2007 4:44:59 PMAFAIL
Interconnection verified at hood #1, one notification device did not function.
FIR07-00431 INSP-Sprinkler Rough-in6/25/20076/25/20076/25/2007 4:41:59 PMPDEFR
Inspection rescheduled per agreement with contractor.
FIR07-00541 INSP-Alarm Testing6/22/20076/25/20076/25/2007 4:40:36 PMAFAIL
The horn/strobe device in the kitchen area failed to function properly upon alarm activation.
FIR07-00528 INSP-Sprinkler Rough-in6/22/20076/25/20076/25/2007 3:31:37 PMAPART
UG fire supply line is approved for cover, noted lacking method for seismic clearance where ductile riser will pass through the floor slab, also missing flange and cap at the top of the riser.
BLD06-03574 FIRE-Final Inspection6/22/20076/25/20076/25/2007 2:59:53 PMAFAIL
Need to repair one emergency light at the waiting area, one fire sprinkler head in a storage closet is cut in too high, need to have the project related fire alarm and fire sprinkler permits called in for final prior to life safety sign off, also need to post suite address numbers.
FIR07-00492 INSP-Alarm Testing6/21/20076/25/20076/25/2007 1:56:58 PMPCANC
mike Phone #: ###-####...............Per conversation with contractor, inspection to be rescheduled.
BLD06-03612 FIRE-Final Inspection6/22/20076/25/20076/25/2007 1:52:40 PMAFAIL
See correction notice left on site for items including provision of approved door hardware at three marked exits, provide current annual inspection for the existing fire sprinkler system, re-attatch one PFE to column #1, the newly installed deck to floor partition at the SE corner of the warehouse disrupts required fire sprinkler system coverage and density, no racking allowed over 8' in height without a separate application and permit, see fire code review notes and approved plans for details and locations of defficiencies.
BLD06-02135 FIRE-Final Inspection6/25/20076/25/20076/25/2007 1:44:45 PMPFAIL
Provide approved hardware at the marked exits-manual thumbturns are not allowed, lower the provided fire extinguisher to 48" max AFF, provide approved hardware at both restroom doors, noted no city stamped plans or plan review notes on site.
FIR07-00070 FIR-Aging Inspection6/25/20076/25/20076/25/2007 12:13:03 PM DONE
wip
BLD07-00591 FIRE-Final Inspection6/22/20076/25/20076/25/2007 12:07:11 PMAPASS
PFE installed as agreed, fire life safety passed inspection.
FIR07-00480 INSP-Final Inspection6/25/20076/25/20076/25/2007 12:05:47 PMPPASS
FA permit finaled.
FIR07-00394 INSP-Final Inspection6/25/20076/25/20076/25/2007 12:05:18 PMPPASS
Noted issues from the previous inspection have been repaired, fire sprinkler permit finaled.
FIR07-00480 INSP-Alarm Testing6/22/20076/25/20076/25/2007 12:03:23 PMAPASS
c/n is complete, fire alarm testing passed.
FIR07-00382 INSP-Final Inspection6/22/20076/25/20076/25/2007 12:02:27 PMAPASS
Fire alarm work passed inspection, permit finaled.
FIR07-00457 INSP-Sprinkler Rough-in/Hydro6/23/20076/25/20076/25/2007 11:45:52 AMAPART
Noted two overspaced heads from an adjacent wall in the remodeled area, the remainder of permit work fire sprinkler modifications are acceptable.
FIR07-00270 INSP-Sprinkler Rough-in6/22/20076/25/20076/25/2007 11:41:52 AMAPART
Required modifications have been completed, OH install is approved for cover.