MIS07-00141
| FIR-Final | 6/25/2007 | 6/25/2007 | 6/25/2007 5:04:17 PM | P | FAIL |
|
|
Met contact on site who could not provide access to the building due to missing keys, no inspection completed.
|
BLD07-00665
| FIRE-Final Inspection | 6/22/2007 | 6/25/2007 | 6/25/2007 4:56:50 PM | A | FAIL |
|
|
Need to repair one emergency light at the main lobby, remove manual thumbturn at the office door, post the provided 2A10BC fire extinguisher on the wall as discussed, need to final the project related fire alarm permit prior to life safety final, noted slider doors at three private dining rooms may not meet hardware accessibility requirements as installed.
|
FIR07-00541
| INSP-Final Inspection | 6/22/2007 | 6/25/2007 | 6/25/2007 4:44:59 PM | A | FAIL |
|
|
Interconnection verified at hood #1, one notification device did not function.
|
FIR07-00431
| INSP-Sprinkler Rough-in | 6/25/2007 | 6/25/2007 | 6/25/2007 4:41:59 PM | P | DEFR |
|
|
Inspection rescheduled per agreement with contractor.
|
FIR07-00541
| INSP-Alarm Testing | 6/22/2007 | 6/25/2007 | 6/25/2007 4:40:36 PM | A | FAIL |
|
|
The horn/strobe device in the kitchen area failed to function properly upon alarm activation.
|
FIR07-00528
| INSP-Sprinkler Rough-in | 6/22/2007 | 6/25/2007 | 6/25/2007 3:31:37 PM | A | PART |
|
|
UG fire supply line is approved for cover, noted lacking method for seismic clearance where ductile riser will pass through the floor slab, also missing flange and cap at the top of the riser.
|
BLD06-03574
| FIRE-Final Inspection | 6/22/2007 | 6/25/2007 | 6/25/2007 2:59:53 PM | A | FAIL |
|
|
Need to repair one emergency light at the waiting area, one fire sprinkler head in a storage closet is cut in too high, need to have the project related fire alarm and fire sprinkler permits called in for final prior to life safety sign off, also need to post suite address numbers.
|
FIR07-00492
| INSP-Alarm Testing | 6/21/2007 | 6/25/2007 | 6/25/2007 1:56:58 PM | P | CANC |
|
|
mike Phone #: ###-####...............Per conversation with contractor, inspection to be rescheduled.
|
BLD06-03612
| FIRE-Final Inspection | 6/22/2007 | 6/25/2007 | 6/25/2007 1:52:40 PM | A | FAIL |
|
|
See correction notice left on site for items including provision of approved door hardware at three marked exits, provide current annual inspection for the existing fire sprinkler system, re-attatch one PFE to column #1, the newly installed deck to floor partition at the SE corner of the warehouse disrupts required fire sprinkler system coverage and density, no racking allowed over 8' in height without a separate application and permit, see fire code review notes and approved plans for details and locations of defficiencies.
|
BLD06-02135
| FIRE-Final Inspection | 6/25/2007 | 6/25/2007 | 6/25/2007 1:44:45 PM | P | FAIL |
|
|
Provide approved hardware at the marked exits-manual thumbturns are not allowed, lower the provided fire extinguisher to 48" max AFF, provide approved hardware at both restroom doors, noted no city stamped plans or plan review notes on site.
|
FIR07-00070
| FIR-Aging Inspection | 6/25/2007 | 6/25/2007 | 6/25/2007 12:13:03 PM | | DONE |
|
|
wip
|
BLD07-00591
| FIRE-Final Inspection | 6/22/2007 | 6/25/2007 | 6/25/2007 12:07:11 PM | A | PASS |
|
|
PFE installed as agreed, fire life safety passed inspection.
|
FIR07-00480
| INSP-Final Inspection | 6/25/2007 | 6/25/2007 | 6/25/2007 12:05:47 PM | P | PASS |
|
|
FA permit finaled.
|
FIR07-00394
| INSP-Final Inspection | 6/25/2007 | 6/25/2007 | 6/25/2007 12:05:18 PM | P | PASS |
|
|
Noted issues from the previous inspection have been repaired, fire sprinkler permit finaled.
|
FIR07-00480
| INSP-Alarm Testing | 6/22/2007 | 6/25/2007 | 6/25/2007 12:03:23 PM | A | PASS |
|
|
c/n is complete, fire alarm testing passed.
|
FIR07-00382
| INSP-Final Inspection | 6/22/2007 | 6/25/2007 | 6/25/2007 12:02:27 PM | A | PASS |
|
|
Fire alarm work passed inspection, permit finaled.
|
FIR07-00457
| INSP-Sprinkler Rough-in/Hydro | 6/23/2007 | 6/25/2007 | 6/25/2007 11:45:52 AM | A | PART |
|
|
Noted two overspaced heads from an adjacent wall in the remodeled area, the remainder of permit work fire sprinkler modifications are acceptable.
|
FIR07-00270
| INSP-Sprinkler Rough-in | 6/22/2007 | 6/25/2007 | 6/25/2007 11:41:52 AM | A | PART |
|
|
Required modifications have been completed, OH install is approved for cover.
|