ELE08-01728
| Electrical Rough-In | 6/25/2008 | 6/25/2008 | 6/25/2008 3:42:00 PM | P | PASS |
|
|
don Phone #: ###-#### ok
|
ELE07-02064
| Final | 6/25/2008 | 6/25/2008 | 6/25/2008 3:16:29 PM | P | PASS |
|
|
jared Phone #: ###-#### ok card signed
|
ELE08-00888
| Final | 6/25/2008 | 6/25/2008 | 6/25/2008 2:56:48 PM | P | FAIL |
|
|
Jeremy Phone #: ###-#### corr. called 110.26(F)(1) clearence for sub panel , 408.4 be specific, 300.12 terminate LFNC to p/s and remove romex too many bends in LFNC, use manufactures listed breakers only at p/s 314.20 box extension at outlet in cabinet wet bar
|
ELE08-01711
| Permanent Service | 6/24/2008 | 6/25/2008 | 6/25/2008 2:03:41 PM | P | CANC |
|
|
Randys cell ###-#### Phone #: ###-#### Internet Inspection Request from: Randy Fletcher see added t/s corr. 314.28 angle pull needs 12" between conuit entries at jbox or use LBS sized properly
|
ELE08-01711
| Temporary Service | 6/25/2008 | 6/25/2008 | 6/25/2008 2:02:02 PM | P | PART |
|
|
Randys cell ###-#### Phone #: ###-#### Internet Inspection Request from: Randy Fletcher power ok for temporary hook up till contr makes correction
|
ELE08-01724
| Electrical Rough-In | 6/25/2008 | 6/25/2008 | 6/25/2008 1:19:03 PM | P | PART |
|
|
PAUL PLEASE CALL PRIOR TO HEADING TO THE SITE Phone #: ###-#### Internet Inspection Request from: Sean DeLacy corr posted contr fixing items 4wire to oven, remove range hood from SABC, address recept spacing right and left of sink? r/i ok
|
ELE08-00657
| Electrical Rough-In | 6/25/2008 | 6/25/2008 | 6/25/2008 12:37:31 PM | P | PART |
|
|
Equal grid and potting compound. Phone #: ###-#### Internet Inspection Request from: Lynn Cable ok
|
ELE08-00701
| ELE-Aging Inspection | 6/25/2008 | 6/25/2008 | 6/25/2008 11:55:12 AM | | PART |
|
|
waiting for listing on water jet equipment
|
ELE07-01578
| ELE-Aging Inspection | 6/25/2008 | 6/25/2008 | 6/25/2008 11:54:14 AM | | DONE |
|
|
|
ELE07-01578
| DOC - Permit Finaled | 6/25/2008 | 6/25/2008 | 6/25/2008 11:54:06 AM | P | PASS |
|
|
no work done on permit contr. never called back
|
ELE08-01015
| ELE-Aging Inspection | 6/25/2008 | 6/25/2008 | 6/25/2008 11:52:28 AM | | DONE |
|
|
wsuc
|
ELE08-01688
| Electrical Rough-In | 6/23/2008 | 6/25/2008 | 6/25/2008 11:47:28 AM | A | FAIL |
|
|
circuit is ready for inspection Phone #: ###-#### Internet Inspection Request from: gary batten called portable a/c shall have factory LCDI or AFCI as part of cord
|
ELE08-01657
| Rough-In Permanent Service | 6/24/2008 | 6/25/2008 | 6/25/2008 11:06:05 AM | A | FAIL |
|
|
Steve Phone #: ###-#### called corr fee due 300.4 nail plates and 11/4" all locations, BCC complete all makeup outside boxes and install box for micro wave
|
ELE08-01112
| Final | 6/24/2008 | 6/25/2008 | 6/25/2008 10:21:40 AM | A | PASS |
|
|
Trent Phone #: ###-#### ok
|
ELE07-00981
| Final | 6/24/2008 | 6/25/2008 | 6/25/2008 9:26:34 AM | A | NR |
|
|
adi Phone #: ###-####
|
ELE08-01643
| Electrical Rough-In | 6/24/2008 | 6/25/2008 | 6/25/2008 9:10:52 AM | A | FAIL |
|
|
randy Phone #: ###-#### fee due corr. called 680.26(B)(5) bond door metal and downspouts, 110.26(F)(1) clearence for subpanel, 100.3(B) use manufactures listed breakers in subpanel also spa manufacture states all conductors #6 copper, BCC no violations to be retained
|
ELE08-01690
| Electrical Rough-In | 6/24/2008 | 6/25/2008 | 6/25/2008 8:09:31 AM | A | PART |
|
|
Jim- underground Phone #: ###-#### ok no ESC attached to project
|
ELE08-01643
| Final | 6/24/2008 | 6/25/2008 | 6/24/2008 12:27:56 PM | A | CANC |
|
|
Final on service upgrade and hot tub Phone #: ###-#### Internet Inspection Request from: Randy Fletcher Inspection cancelled from web by: Randy Fletcher
|