Inspections for the day of: Wednesday, June 25, 2008.
Number of inspections: 17
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorForrest France
TitleFIRE INSPECTOR
Phone #794-1981
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
FIR08-00256 INSP-Sprinkler Rough-in/Hydro6/24/20086/25/20086/26/2008 10:06:14 AMAPART
UG fire supply line hydrostatic testing completed.
FIR07-00672 INSP-Final Inspection6/25/20086/25/20086/25/2008 4:25:30 PMPPART
Tested all pull stations, tested all horns and strobes.KR
FIR04-00673 INSP-Final Inspection6/25/20086/25/20086/25/2008 3:32:51 PMPPART
Apt. units 812 and 812 1/2 smoke alarms tested okay.
FIR08-00256 INSP-Supply line flush6/24/20086/25/20086/25/2008 3:23:34 PMANR
Need to coordinate inspection with United Water Co. as discussed.
FIR08-00423 INSP-Final Inspection6/25/20086/25/20086/25/2008 3:22:42 PMPPASS
Scope of fire sprinkler demo work completed, permit finaled.
FIR08-00370 INSP-Sprinkler Rough-in/Hydro6/24/20086/25/20086/25/2008 3:21:31 PMAFAIL
Need to add one upright head due to overspacing, missing hanger at one armover, FDC is obstructed by landscaping (GC agreed to remove plants as necessary), SW heads at dormers are okay, remainder of rough-in is acceptable.
FIR07-00309 INSP-Sprinkler Rough-in/Hydro6/25/20086/25/20086/25/2008 1:22:42 PMPDONE
Ok to cover, Sprinkler head moved per Troys notes. KR
BLD08-00080 FIRE-Final Inspection6/24/20086/25/20086/25/2008 12:39:27 PMPNR
Bill, please call 30 minutes prior; Phone #: ###-#### Internet Inspection Request from: Cathy Weisshaupt
BLD07-03243 BLD-Final6/25/20086/25/20086/25/2008 12:27:48 PMPCANC
BLD07-03243 FIRE-Final Inspection6/25/20086/25/20086/25/2008 12:21:06 PMPPASS
Fire life safety complete. KR
FIR08-00432 INSP-Final Inspection6/24/20086/25/20086/25/2008 12:18:25 PMAPASS
Firen alarm issues resolved per plan notes.Duct smoke test complete. KR
FIR08-00327 INSP-Sprinkler Rough-in6/25/20086/25/20086/25/2008 12:06:11 PMPPART
Verified relocated pendent at the reception entry, tenting at the wet piping is acceptable, OH install is okay for cover at the sheetrock ceilings this TI only.
FIR08-00209 INSP-Sprinkler Rough-in6/24/20086/25/20086/25/2008 11:40:45 AMAFAIL
See stamped plan set for locations in need of adjustment including two overspaced pendent heads at the nurse station and three SSU's above the X-ray room which exceed min. spacing, also notified contractor to call in the shell FIR permit for rough-in inspection at next scheduled visit.
FIR08-00418 INSP-Sprinkler Rough-in/Hydro6/24/20086/25/20086/25/2008 11:35:31 AMAPART
C/N items repaired, OH fire sprinkler system modifications for the tenant area are approved for cover at the drop ceilings.
BLD07-01188 FIRE-Final Inspection6/24/20086/25/20086/25/2008 11:33:36 AMAPASS
Fire life safety inspection passed.
FIR08-00121 INSP-Final Inspection6/24/20086/25/20086/25/2008 11:32:52 AMAPASS
Remainder of items on the correction notice verified for compliance, final fire alarm inspection passed, permit finaled.
FIR08-00152 FIR-Aging Inspection6/25/20086/25/20086/25/2008 9:22:46 AM DONE
Work in progress, under construction.