FIR09-00083
| FIR-Aging Inspection | 6/25/2009 | 6/25/2009 | 6/25/2009 5:21:42 PM | | DONE |
|
|
In progress
|
FIR09-00311
| INSP-Sprinkler Rough-in/Hydro | 6/19/2009 | 6/25/2009 | 6/25/2009 5:20:50 PM | A | DEFR |
|
|
Inspection scheduled per contractor early AM to accomodate tenant request.
|
FIR09-00249
| INSP-Conference | 6/25/2009 | 6/25/2009 | 6/25/2009 5:14:36 PM | P | DONE |
|
|
Regarding fire sprinkler system monitoring and interconnect with the FACP.
|
FIR09-00320
| INSP-Final Inspection | 6/19/2009 | 6/25/2009 | 6/25/2009 5:13:26 PM | P | FAIL |
|
|
AES battery and antenna failure did not indicate trouble condition at the FACP. Remainder of permit work tested okay.
|
FIR05-00698
| INSP-Final Inspection | 6/24/2009 | 6/25/2009 | 6/25/2009 5:09:28 PM | A | NR |
|
|
Need to provide approved plan resubmittals indicating field modifications and changes to system installation which differ significantly from the original design. Also need to coordinate field acceptance testing with the fire sprinkler contractor for system interconnections.
|
FIR09-00072
| FIR-Aging Inspection | 6/25/2009 | 6/25/2009 | 6/25/2009 12:48:36 PM | | DONE |
|
|
Work in progress.
|
BLD09-00974
| FIRE-Final Inspection | 6/24/2009 | 6/25/2009 | 6/25/2009 12:47:44 PM | A | FAIL |
|
|
Provide current annual certification for both fire extinguishers, lower mounting height at the west side extinguisher, remove the manual thumbturn at the main entry/exit and provide approved exit hardware, terminate exposed electrical wires in a junction box.
|
BLD08-02460
| FIRE-Final Inspection | 6/24/2009 | 6/25/2009 | 6/25/2009 12:43:13 PM | A | PART |
|
|
Fire life safety inspection completed acceptable for the scope of remodel. Final pending fire alarm upgrade work at the common exit corridors per agreement on file.
|
BLD07-01091
| FIRE-Final Inspection | 6/25/2009 | 6/25/2009 | 6/25/2009 12:41:08 PM | A | PASS |
|
|
Fire life safety approved for final status, inspection record signed.
|