FIR10-00292
| INSP-Final Inspection | 6/25/2010 | 6/25/2010 | 6/25/2010 4:57:51 PM | P | PASS |
|
|
Fire sprinkler permit okay for final.
|
FIR10-00292
| INSP-Sprinkler Rough-in | 6/25/2010 | 6/25/2010 | 6/25/2010 4:57:17 PM | P | PASS |
|
|
Overhead rough-in okayed for cover.
|
FIR10-00267
| INSP-Final Inspection | 6/23/2010 | 6/25/2010 | 6/25/2010 4:54:31 PM | P | PASS |
|
|
Scope of fire alarm work passed field testing, permit finaled.
|
FIR10-00259
| INSP-Final Inspection | 6/24/2010 | 6/25/2010 | 6/25/2010 4:53:26 PM | A | PASS |
|
|
Fire sprinkler permit approved for final status.
|
FIR10-00216
| INSP-Final Inspection | 6/24/2010 | 6/25/2010 | 6/25/2010 4:52:47 PM | A | PASS |
|
|
Fire sprinkler permit finaled.
|
FIR08-00813
| FIR-Aging Inspection | 6/25/2010 | 6/25/2010 | 6/25/2010 12:44:16 PM | | FAIL |
|
|
Contractor has failed to request site inspection for permit work.
|
FIR08-00820
| FIR-Aging Inspection | 6/25/2010 | 6/25/2010 | 6/25/2010 12:42:10 PM | | PEND |
|
|
Contractor must request site inspection for permit final.
|
FIR08-00818
| FIR-Aging Inspection | 6/25/2010 | 6/25/2010 | 6/25/2010 12:40:36 PM | | FAIL |
|
|
Netcon rating is not satisfactory- ref. activity notes. Contractor to request reinspection upon repair.
|
FIR10-00228
| INSP-Final Inspection | 6/25/2010 | 6/25/2010 | 6/25/2010 12:35:49 PM | P | PASS |
|
|
Fire sprinkler permit work approved for final status. Inspection passed.
|
BLD10-00791
| FIRE-Final Inspection | 6/24/2010 | 6/25/2010 | 6/25/2010 12:34:57 PM | A | PASS |
|
|
Noted corrections field verified for compliance, fire life safety finaled.
|
BLD10-01327
| FIRE-Final Inspection | 6/23/2010 | 6/25/2010 | 6/25/2010 12:18:15 PM | A | FAIL |
|
|
Need to remove the manual thumbturn at the main entry/exit door and provide "door to..." signage, emergency lights at the shop area are not functional, provide approved hardware or remove the exit sign at the exterior door adjacent to the restrooms. Discussed fire extinguisher placement. Refer to permit documents for listing of general requirements.
|
FIR10-00259
| INSP-Sprinkler Rough-in/Hydro | 6/25/2010 | 6/25/2010 | 6/25/2010 12:12:05 PM | A | PART |
|
|
Overhead fire sprinkler work appears satisfactory, missing permit documents and approved plans on site.
|
BLD10-00999
| FIRE-Final Inspection | 6/25/2010 | 6/25/2010 | 6/25/2010 12:10:15 PM | A | FAIL |
|
|
Door hardware and exit sign issues at the S1 area.
|
FIR10-00272
| INSP-Final Inspection | 6/23/2010 | 6/25/2010 | 6/25/2010 11:06:02 AM | A | PASS |
|
|
Fire alarm passed inspection, permit finaled.
|
FIR10-00281
| INSP-Final Inspection | 6/24/2010 | 6/25/2010 | 6/25/2010 12:00:00 AM | A | CANC |
|
|
Could not be finaled due to missing ceiling tile. Was changed to a rough in inspection instead
Final - Contact: Jeff Inspection requested from web by: Alicia Pauley Phone #: ###-#### x1234
|