Inspections for the day of: Monday, June 25, 2012.
Number of inspections: 13
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorForrest France
TitleFIRE INSPECTOR
Phone #794-1981
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
BLD12-01320 FIRE-Final Inspection6/22/20126/25/20126/25/2012 5:00:05 PMPPASS
Field verified fire extinguisher has been provided. Main entry door hardware is still not correct- need to post "door to remain unlocked while building is occupied" signage and remove the manual thumbturn in favor of a keyed lock per allowable exception. Hardware issues to be finished prior to structural final inspection as discussed and agreed.
FIR12-00276 INSP-Sprinkler Rough-in/Hydro6/25/20126/25/20126/25/2012 4:56:03 PMPPART
Okay to cover overhead work at the mens and womens restroom including the entry vestibule and two pendent heads to the west of the new partition wall. See plan set for marked and dated areas.
FIR11-00567 INSP-Final Inspection6/25/20126/25/20126/25/2012 4:14:27 PMPFAIL
See fire plan review notes item #1 regarding system smoke detectors at the sleeping rooms, tamper switch at the forward flow control valve is wired normally open, revise panel to eliminate the autotest communication error due to AES transmitter.
FIR12-00041 INSP-Final Inspection6/25/20126/25/20126/25/2012 4:06:51 PMPPEND
Pending alarm permit finals
BLD12-00451 FIRE-Sprinkler Rough-in6/25/20126/25/20126/25/2012 4:05:12 PMPPART
Brian: FIR 12-00276 Phone #: ###-#### >> Inspection requested via web by Roger Friend *Okay to cover at the restrooms per initialed and dated annotations on approved sprinkler drawings.*
BLD11-01555 FIRE-Final Inspection6/22/20126/25/20126/25/2012 2:41:41 PMACANC
Overbooked
BLD12-00666 FIRE-Final Inspection6/22/20126/25/20126/25/2012 2:24:57 PMAPASS
Previous items verified for completion. Life safety final passed.
BLD12-00926 FIRE-Conference6/25/20126/25/20126/25/2012 1:21:40 PMPDONE
Please call prior -- Vic Phone #: ###-#### Conversation with contractor regarding IBC 719.1 and 719.3.
BLD12-00383 FIRE-Final Inspection6/22/20126/25/20126/25/2012 1:14:06 PMAPASS
Fire life safety inspection passed. Contractor to provide address numbers at the fuel island canopy as discussed.
BLD11-02880 FIRE-Final Inspection6/22/20126/25/20126/25/2012 12:46:29 PMAPASS
Fire life safety inspection completed satisfactory.
BLD12-01148 FIRE-Final Inspection6/22/20126/25/20126/25/2012 12:45:39 PMAFAIL
Exit signs at the corridor are not functional on battery backup, one new office is missing fire sprinkler coverage, existing FP system is overdue annual certification. Modifications to the fire sprinkler system will require a separate permit.
BLD11-02564 FIRE-Final Inspection6/22/20126/25/20126/25/2012 12:38:57 PMAPASS
Scope of permit work completed. Life safety passed.
BLD12-01213 FIRE-Final Inspection6/22/20126/25/20126/25/2012 10:33:44 AMAPASS
Fire life safety is acceptable pending building address numbers are posted and the keyed lock at the second storefront exit is blanked or removed (mag lock hardware has been installed). Items to be completed prior to structural final approval.