BLD12-01320
| FIRE-Final Inspection | 6/22/2012 | 6/25/2012 | 6/25/2012 5:00:05 PM | P | PASS |
|
|
Field verified fire extinguisher has been provided. Main entry door hardware is still not correct- need to post "door to remain unlocked while building is occupied" signage and remove the manual thumbturn in favor of a keyed lock per allowable exception. Hardware issues to be finished prior to structural final inspection as discussed and agreed.
|
FIR12-00276
| INSP-Sprinkler Rough-in/Hydro | 6/25/2012 | 6/25/2012 | 6/25/2012 4:56:03 PM | P | PART |
|
|
Okay to cover overhead work at the mens and womens restroom including the entry vestibule and two pendent heads to the west of the new partition wall. See plan set for marked and dated areas.
|
FIR11-00567
| INSP-Final Inspection | 6/25/2012 | 6/25/2012 | 6/25/2012 4:14:27 PM | P | FAIL |
|
|
See fire plan review notes item #1 regarding system smoke detectors at the sleeping rooms, tamper switch at the forward flow control valve is wired normally open, revise panel to eliminate the autotest communication error due to AES transmitter.
|
FIR12-00041
| INSP-Final Inspection | 6/25/2012 | 6/25/2012 | 6/25/2012 4:06:51 PM | P | PEND |
|
|
Pending alarm permit finals
|
BLD12-00451
| FIRE-Sprinkler Rough-in | 6/25/2012 | 6/25/2012 | 6/25/2012 4:05:12 PM | P | PART |
|
|
Brian: FIR 12-00276 Phone #: ###-#### >> Inspection requested via web by Roger Friend *Okay to cover at the restrooms per initialed and dated annotations on approved sprinkler drawings.*
|
BLD11-01555
| FIRE-Final Inspection | 6/22/2012 | 6/25/2012 | 6/25/2012 2:41:41 PM | A | CANC |
|
|
Overbooked
|
BLD12-00666
| FIRE-Final Inspection | 6/22/2012 | 6/25/2012 | 6/25/2012 2:24:57 PM | A | PASS |
|
|
Previous items verified for completion. Life safety final passed.
|
BLD12-00926
| FIRE-Conference | 6/25/2012 | 6/25/2012 | 6/25/2012 1:21:40 PM | P | DONE |
|
|
Please call prior -- Vic Phone #: ###-#### Conversation with contractor regarding IBC 719.1 and 719.3.
|
BLD12-00383
| FIRE-Final Inspection | 6/22/2012 | 6/25/2012 | 6/25/2012 1:14:06 PM | A | PASS |
|
|
Fire life safety inspection passed. Contractor to provide address numbers at the fuel island canopy as discussed.
|
BLD11-02880
| FIRE-Final Inspection | 6/22/2012 | 6/25/2012 | 6/25/2012 12:46:29 PM | A | PASS |
|
|
Fire life safety inspection completed satisfactory.
|
BLD12-01148
| FIRE-Final Inspection | 6/22/2012 | 6/25/2012 | 6/25/2012 12:45:39 PM | A | FAIL |
|
|
Exit signs at the corridor are not functional on battery backup, one new office is missing fire sprinkler coverage, existing FP system is overdue annual certification. Modifications to the fire sprinkler system will require a separate permit.
|
BLD11-02564
| FIRE-Final Inspection | 6/22/2012 | 6/25/2012 | 6/25/2012 12:38:57 PM | A | PASS |
|
|
Scope of permit work completed. Life safety passed.
|
BLD12-01213
| FIRE-Final Inspection | 6/22/2012 | 6/25/2012 | 6/25/2012 10:33:44 AM | A | PASS |
|
|
Fire life safety is acceptable pending building address numbers are posted and the keyed lock at the second storefront exit is blanked or removed (mag lock hardware has been installed). Items to be completed prior to structural final approval.
|