Inspections for the day of: Tuesday, June 25, 2013.
Number of inspections: 17
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorDaryl DeGrange
TitleELE-INSPECTION SUPV
Phone #794-1379
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
ELE12-00617 ELE-Aging Inspection6/25/20136/25/20137/3/2013 12:17:08 PM DONE
left message with contractor
ELE12-00643 ELE-Aging Inspection6/25/20136/25/20137/3/2013 6:20:33 AM DONE
contractor will contact homeowner for access
ELE13-01424 Final6/24/20136/25/20136/25/2013 3:33:08 PMPPASS
trying for a final call corey with questions Phone #: ###-#### >> Inspection requested via web by Don Lustig final ok
ELE13-01423 Final6/24/20136/25/20136/25/2013 3:29:41 PMPPASS
trying for a final call corey with questions thanks Phone #: ###-#### >> Inspection requested via web by Don Lustig final ok
ELE12-00632 ELE-Aging Inspection6/25/20136/25/20136/25/2013 3:07:44 PM DONE
see final
ELE12-00632 Final6/25/20136/25/20136/25/2013 3:04:16 PMPPASS
corrections done,job complete final ok
ELE12-00532 Final6/18/20136/25/20136/25/2013 2:27:13 PMPPASS
requests after 2 pm * Heather Phone #: ###-#### job complete final ok
ELE13-00953 Final6/25/20136/25/20136/25/2013 1:58:34 PMPPASS
Phone #: ###-#### >> Inspection requested via web by daniel bibikov final ok
ELE13-01560 Rough-In Permanent Service6/25/20136/25/20136/25/2013 1:44:39 PMPFAIL
Phone #: ###-#### >> Inspection requested via web by daniel bibikov NEC 300.4 Nail plates and NM 1 1/4 spacing from face of framing member, home runs in garage
ELE13-01616 Electrical Rough-In6/25/20136/25/20136/25/2013 1:03:40 PMPFAIL
walls Phone #: ###-#### >> Inspection requested via web by Bryan McLaughlin NEC 330.12 Protect from physical damage 1 1/4 spacing from face of framing member. Junction boxes shall not rendered inaccessible
ELE13-01521 Final6/25/20136/25/20136/25/2013 12:23:46 PMPFAIL
warren Phone #: ###-#### Grounding electrode conductor must terminate in ground bar not neutral bar. Complete panel directory, NEC 406.8(B) Requires receptacle installed in wet locations to be listed weather resistant type
ELE13-01526 Permanent Service6/24/20136/25/20136/25/2013 9:43:31 AMAPASS
casey Phone #: ###-#### p/s o/h rec ok
ELE13-01620 Permanent Service6/24/20136/25/20136/25/2013 9:23:02 AMAPASS
Chad Phone #: ###-#### rough-in ok cover trench and unattached structure
ELE13-01322 Electrical Rough-In6/24/20136/25/20136/25/2013 8:51:54 AMAPASS
Rough inspection of the knee wall in the pharmacy and mechanical room walls. Contact on the job is Justin Bieker. Phone #: ###-#### >> Inspection requested via web by Richard Montgomery rough-in ok cover
ELE13-01379 Electrical Rough-In6/24/20136/25/20136/25/2013 8:35:00 AMAPASS
ceiling cover is needed call corey with questions thanks Phone #: ###-#### >> Inspection requested via web by Don Lustig rough-in ok cover ceiling grid
ELE13-01125 Final6/24/20136/25/20136/25/2013 8:11:29 AMAPASS
Phone #: ###-#### >> Inspection requested via web by Zane Robertson final ok
ELE13-00627 Final6/24/20136/25/20136/25/2013 8:00:00 AMAPASS
Garage code 0243 Phone #: ###-#### >> Inspection requested via web by Joe Thomas final ok