Inspections for the day of: Wednesday, June 25, 2014.
Number of inspections: 15
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorForrest France
TitleFIRE INSPECTOR
Phone #794-1981
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
FIR13-00542 INSP-Final Inspection6/24/20146/25/20146/27/2014 1:49:28 PMPDONE
FIR14-00353 INSP-Sprinkler Rough-in6/25/20146/25/20146/27/2014 1:48:36 PMPPART
Okay to cover overhead fire sprinkler work. Tenting 2nd floor okayed. Need to provide intermediate temp heads at the furnace closets.
FIR14-00280 INSP-Sprinkler Rough-in6/24/20146/25/20146/25/2014 4:05:42 PMPPART
Second floor fire sprinkler work passed cover inspection with the exception of one overspaced area in the corridor. Also noted one damaged head to be replaced. Locations marked and dated on approved plans.
BLD13-03370 FIRE-Final Inspection6/24/20146/25/20146/25/2014 4:02:04 PMPPASS
Noted corrections completed. Fire life safety finaled.
FIR14-00269 INSP-Sprinkler Rough-in6/25/20146/25/20146/25/2014 4:01:21 PMPPART
Sheetrock soffits as dated on plans okayed for cover. Modifications at the atrium area to show on plan mod., need to add one head below ductwork at the concealed space per discussion.
BLD14-00699 FIRE-Final Inspection6/25/20146/25/20146/25/2014 2:26:21 PMPPASS
Fire life safety inspection passed. Need to post max occupant load signage per plan review at the A-3 area prior to structural final.
FIR14-00387 INSP-Sprinkler Rough-in6/25/20146/25/20146/25/2014 1:58:46 PMPDEFR
Installation to match plans as discussed.
BLD13-03281 FIRE-Conference6/24/20146/25/20146/25/2014 1:57:43 PMPDONE
Tom Phone #: ###-#### *Completed by C. Hanson*
FIR14-00353 INSP-Sprinkler Rough-in/Hydro6/24/20146/25/20146/25/2014 1:55:34 PMAPART
OH hydrostatic test completed satisfactory. Tenting needs adjusted at the second floor south apt.
FIR14-00228 INSP-Conference6/24/20146/25/20146/25/2014 12:09:17 PMADONE
Regarding fire sprinkler coverage
FIR14-00275 INSP-Final Inspection6/25/20146/25/20146/25/2014 11:14:41 AMPCANC
Robert is the contact. Thanks Phone #: ###-#### >> Inspection requested via web by Stan Beus Inspection cancelled from web by: Stan Beus
BLD14-01677 FIRE-Final Inspection6/24/20146/25/20146/25/2014 10:24:14 AMAPASS
Life safety approved pending door hardware at the back warehouse exit meets plan review conditions. To be completed prior to structural final.
FIR14-00264 INSP-Final Inspection6/24/20146/25/20146/25/2014 10:21:45 AMAPART
Overhead fire sprinkler work at the clouded areas as marked and dated on approved plans in phase two and three approved for ceiling cover.
FIR14-00275 INSP-Final Inspection6/24/20146/25/20146/25/2014 10:16:17 AMACANC
Robert is the contact. Thanks Phone #: ###-#### >> Inspection requested via web by Stan Beus Inspection cancelled from web by: Stan Beus
BLD14-00653 FIRE-Final Inspection6/24/20146/25/20146/25/2014 7:14:16 AMANR
Need project related hood suppression system permit, hood inspection and final prior to building fire life safety approval. Refer to fire code review notes items #3 and 4 for details. Also discussed life safety inspection items including door hardware, exit signs, EM lighting, PFE.