BLD15-01490
| FIRE-Final Inspection | 6/23/2015 | 6/25/2015 | 6/25/2015 2:17:12 PM | A | PASS |
|
|
Life fire safety passed/complete
|
FIR15-00359
| INSP-Sprinkler Rough-in | 6/24/2015 | 6/25/2015 | 6/25/2015 2:16:30 PM | P | PASS |
|
|
Overhead sprinkler piping/tenting approved for cover
|
FIR15-00358
| INSP-Supply line flush | 6/24/2015 | 6/25/2015 | 6/25/2015 2:15:21 PM | P | DONE |
|
|
Supply line fush passed/complete
|
FIR15-00306
| INSP-Final Inspection | 6/24/2015 | 6/25/2015 | 6/25/2015 1:41:38 PM | P | PASS |
|
|
As builds provided by contractor, horns and strobes not synching corrected, alarm inspection passed/complete
|
FIR15-00078
| INSP-Alarm Testing | 6/24/2015 | 6/25/2015 | 6/25/2015 12:07:22 PM | P | PART |
|
|
24 hr air test passed/complete
|
FIR15-00226
| INSP-Final Inspection | 6/24/2015 | 6/25/2015 | 6/25/2015 11:21:46 AM | P | PART |
|
|
Contractor is to submit as-build drawings for addition of vestibules at main entries causing overspace issue, TVFP added fire sprinkler heads (One head off of one inch, total of 3 saddle tapped on branch line) around vestibules to accomidate new install and correct overspace issue.
|
FIR14-00838
| INSP-Final Inspection | 6/25/2015 | 6/25/2015 | 6/25/2015 9:57:40 AM | A | PASS |
|
|
Fire alarm inspection passed/complete
|
BLD15-00763
| FIRE-Final Inspection | 6/24/2015 | 6/25/2015 | 6/25/2015 9:00:29 AM | A | PASS |
|
|
Amendment made to original city approved drawings, removal of exit light & installation of lockable door for an area on second floor mezzanine no longer designated as emergency exit/egress. Decorative glass panel installed with new door, causing an overspace issue with fire sprinklers, new sprinkler added on other side of glass panel to provide adequate sprinkler protection, correcting the overspaced issue. Life fire safety inspection passed/complete
|
FIR15-00208
| INSP-Sprinkler Rough-in | 6/24/2015 | 6/25/2015 | 6/25/2015 8:35:40 AM | A | PART |
|
|
Entire Second floor approved for cover
|
FIR15-00381
| INSP-Final Inspection | 6/24/2015 | 6/25/2015 | 6/25/2015 8:15:18 AM | A | PASS |
|
|
Final fire sprinkler inspection passed/complete
|