Inspections for the day of: Thursday, June 25, 2015.
Number of inspections: 10
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorJim Page
TitleFIRE INSPECTOR
Phone #208-914-5431
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
BLD15-01490 FIRE-Final Inspection6/23/20156/25/20156/25/2015 2:17:12 PMAPASS
Life fire safety passed/complete
FIR15-00359 INSP-Sprinkler Rough-in6/24/20156/25/20156/25/2015 2:16:30 PMPPASS
Overhead sprinkler piping/tenting approved for cover
FIR15-00358 INSP-Supply line flush6/24/20156/25/20156/25/2015 2:15:21 PMPDONE
Supply line fush passed/complete
FIR15-00306 INSP-Final Inspection6/24/20156/25/20156/25/2015 1:41:38 PMPPASS
As builds provided by contractor, horns and strobes not synching corrected, alarm inspection passed/complete
FIR15-00078 INSP-Alarm Testing6/24/20156/25/20156/25/2015 12:07:22 PMPPART
24 hr air test passed/complete
FIR15-00226 INSP-Final Inspection6/24/20156/25/20156/25/2015 11:21:46 AMPPART
Contractor is to submit as-build drawings for addition of vestibules at main entries causing overspace issue, TVFP added fire sprinkler heads (One head off of one inch, total of 3 saddle tapped on branch line) around vestibules to accomidate new install and correct overspace issue.
FIR14-00838 INSP-Final Inspection6/25/20156/25/20156/25/2015 9:57:40 AMAPASS
Fire alarm inspection passed/complete
BLD15-00763 FIRE-Final Inspection6/24/20156/25/20156/25/2015 9:00:29 AMAPASS
Amendment made to original city approved drawings, removal of exit light & installation of lockable door for an area on second floor mezzanine no longer designated as emergency exit/egress. Decorative glass panel installed with new door, causing an overspace issue with fire sprinklers, new sprinkler added on other side of glass panel to provide adequate sprinkler protection, correcting the overspaced issue. Life fire safety inspection passed/complete
FIR15-00208 INSP-Sprinkler Rough-in6/24/20156/25/20156/25/2015 8:35:40 AMAPART
Entire Second floor approved for cover
FIR15-00381 INSP-Final Inspection6/24/20156/25/20156/25/2015 8:15:18 AMAPASS
Final fire sprinkler inspection passed/complete