Inspections for the day of: Monday, June 25, 2018.
Number of inspections: 12
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorRock A. Hudson
TitleELE-INSPECTOR
Phone #794-6794
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
ELE18-02357 Conference6/25/20186/25/20186/25/2018 4:10:21 PMPDONE
Corka--please call 20 mins before Phone #: ###-####
Discussed service change to 200 amps. Shall provide 3' from operable windows, size of service entrance conductors, grounding electrode system to include metal underground water pipe if water main is still metal. Owner felt addition of breakers equalled 390 amps of power being used. Informed how service calculations are done and encouraged to test amperage under heavy load to see what actual draw is.
ELE18-00776 Final6/22/20186/25/20186/25/2018 3:14:06 PMPPASS
Phone #: ###-#### Inspection requested via web by JENNY EMEL
All receptacles in break area are GFCI protected, 4- 2 pole receptacles in lab not required to be GFCI protected due to not being used as a kitchen and not located with in 6' of a sink. Final ok
ELE17-01337 Final6/25/20186/25/20186/25/2018 3:13:55 PMPPART
Guest rooms on floor 1 not ready, Laundry equipment not wired but in place wiring blanked off, level 1 west baths vanities blanked off, Floor receptacles thru out level 1 blanked off. Signed TCO phase 1 only. Phase 1 and guest rooms levels 2 thru 5 TCO ok
ELE18-01457 Final6/25/20186/25/20186/25/2018 2:10:52 PMPPASS
Phone #: ###-#### Inspection requested via web by Brad Girard
No card posted. Final ok
ELE18-02334 Final6/25/20186/25/20186/25/2018 2:09:56 PMPPASS
Phone #: ###-#### Inspection requested via web by Brad Girard Final ok
ELE18-02334 Electrical Rough-In6/25/20186/25/20186/25/2018 2:09:56 PMPPASS
Phone #: ###-#### Inspection requested via web by Brad Girard
Grid rough in ok cover
ELE18-02283 Final6/22/20186/25/20186/25/2018 1:01:59 PMAFAIL
Contact name is Bill Canfield Phone #: ###-#### Inspection requested via web by Tyler Ridley
210.63 Heating, Air-Conditioning, and Refrigeration Equipment Outlet. A 125-volt, single-phase, 15- or 20-ampere-rated receptacle outlet shall be installed at an accessible location for the servicing of heating, air-conditioning, and refrigeration equipment. The receptacle shall be located on the same level and within 7.5 m (25 ft) of the heating, air-conditioning, and refrigeration equipment. The receptacle outlet shall not be connected to the load side of the equipment disconnecting means.
ELE17-04065 Electrical Rough-In6/22/20186/25/20186/25/2018 10:26:02 AMAPASS
Ceiling cover. Danny is the contact Phone #: ###-#### Inspection requested via web by Buster Bowen
Basement grid rough in ok cover
ELE18-02360 Conference6/22/20186/25/20186/25/2018 9:42:43 AMADONE
Please call ahead for access - David Phone #: ###-####
Discussed moving 3-way switch near entrance to house from garage. Done at time of conference. Also adding receptacle in garage on north wall. OK to come off existing circuit and installing a tamper resistant GFCI protected receptacle. Gave copy of most frequently asked questions. Will call for rough in inspection when ready.
ELE18-01353 Final6/22/20186/25/20186/25/2018 9:17:31 AMAFAIL
Garage code is 1280 Phone #: ###-#### Inspection requested via web by TOM BICANDI
210.52- Each residence shall have a receptacle outlet installed at front and rear of house. Front receptacle not installed.
314.20- Boxes installed in a combustible material shall be flush with surface or have an extension ring installed. Master bath vanity in cabinets at left and right.
ELE18-02338 Electrical Rough-In6/21/20186/25/20186/25/2018 8:45:44 AMAPASS
garage access code 1001e Phone #: ###-#### Inspection requested via web by Alan Lusk Rough in ok cover
ELE18-02338 Permanent Service6/25/20186/25/20186/25/2018 8:45:35 AMPPASS
garage access code 1001e Phone #: ###-#### Inspection requested via web by Alan Lusk p/s u/g n ok