ELE18-02271
| Electrical Rough-In | 6/25/2018 | 6/25/2018 | 6/25/2018 1:51:08 PM | P | NR |
|
|
I will call at noon to schedule a time to meet you at project Phone #: ###-#### Inspection requested via web by Jesse Simpson Need to remove panels from roof and reschedule final
|
ELE18-01858
| Electrical Rough-In | 6/25/2018 | 6/25/2018 | 6/25/2018 1:50:30 PM | P | PASS |
|
|
Wall cover Phone #: ###-#### Inspection requested via web by cris flores 1st floor 3 appartments only
|
ELE18-00545
| Electrical Rough-In | 6/25/2018 | 6/25/2018 | 6/25/2018 1:32:38 PM | P | PASS |
|
|
John will be there today. 2nd number Graham--###-#### Phone #: ###-#### original layout changed. Down kitchen ok to cover
|
ELE18-02356
| Electrical Rough-In | 6/22/2018 | 6/25/2018 | 6/25/2018 1:11:28 PM | P | FAIL |
|
|
Phone #: ###-#### Inspection requested via web by steve ragan Flat cable shall not be secured on edge, NM cable shall be secured within 8in of box and every4.5ft, cable sheething shall extend 1/4in inside box(hall vanity light) nail plates through out, Bath vanity circuit shall be 20amp and shall serve no others, recep shall be within 36in of vanity basin,Master bed switch box overfilled,14awg on 20amp circuit( Master bed fan and master vanity lights), Screw on boxes shall be listed for the purpose( Master vanity switch)
|
ELE18-02116
| Electrical Rough-In | 6/25/2018 | 6/25/2018 | 6/25/2018 10:24:11 AM | A | PASS |
|
|
Contact: Randy Shipley.... underground inspection please Phone #: ###-#### Inspection requested via web by Deb Gooden Underground only ok to cover
|
ELE18-01724
| Electrical Rough-In | 6/23/2018 | 6/25/2018 | 6/25/2018 10:23:42 AM | A | PASS |
|
|
light pole bases Phone #: ###-#### Inspection requested via web by Lee VanSchoiack Pole bases And underground only ok to cover
|
ELE18-00656
| Final | 6/21/2018 | 6/25/2018 | 6/25/2018 9:59:47 AM | A | PASS |
|
|
Danny is the contact Phone #: ###-#### Inspection requested via web by Buster Bowen Final ok
|
ELE18-02210
| Rough-In Permanent Service | 6/22/2018 | 6/25/2018 | 6/25/2018 8:59:11 AM | A | PASS |
|
|
Phone #: ###-#### Inspection requested via web by Bob Glenn rough in ok p/s u/g n ok
|
ELE18-02325
| Electrical Rough-In | 6/21/2018 | 6/25/2018 | 6/25/2018 8:42:48 AM | A | NR |
|
|
Garage access code 1001e Phone #: ###-#### Inspection requested via web by Alan Lusk Called in by mistake
|
ELE18-02356
| Electrical Rough-In | 6/22/2018 | 6/25/2018 | 6/22/2018 12:46:56 PM | A | CANC |
|
|
Phone #: ###-#### >> Inspection requested via web by steve ragan Inspection cancelled from web by: steve ragan
|