MEC18-02921
| Final | 6/22/2018 | 6/25/2018 | 6/25/2018 1:31:05 PM | A | FAIL |
|
|
Contact: John Please call 30min prior to inspection so the contact can meet with inspector onsite. Phone #: ###-#### Inspection requested via web by RM Mechanical Quick response sprinkler heads to be installed in existing corridor to derate the corridor assembly. Existing CMU wall separating the clinic and corridor is now a fire barrier. Angles at fire damper are required to be all around the damper at corridor side. Ok to remove rated sheetrock ceiling to install the damper per manufacturer installation instructions.
|