FIR18-00052
| INSP-Final Inspection | 6/25/2018 | 6/25/2018 | 6/26/2018 8:15:15 AM | P | CANC |
|
|
Kc Strykowski - Tech Phone #: ###-#### Inspection requested via web by John Siewert
|
BLD17-02419
| FIRE-Final Inspection | 6/25/2018 | 6/25/2018 | 6/25/2018 3:52:28 PM | P | FAIL |
|
|
Only 1 smoke detector in the unit 102 would sound when test buttons was pushed, smoke detectors in the units all need to sound when smoke detection audible is activated.
Phone #: ###-#### Inspection requested via web by David Scaggs
|
BLD17-02413
| FIRE-Final Inspection | 6/25/2018 | 6/25/2018 | 6/25/2018 3:38:10 PM | P | PASS |
|
|
Fire sprinkler inspection complete, fire alarm inspection complete, fire extinguishers are mounted under kitchen cabinets, knox box is located on the north side of building next to FDC. Final life fire safety i nspection complete.
Phone #: ###-#### Inspection requested via web by David Scaggs
|
FIR17-00267
| INSP-Final Inspection | 6/22/2018 | 6/25/2018 | 6/25/2018 3:11:37 PM | P | PASS |
|
|
Final fire sprinkler inspection complete.
Contact Ken Orahood - 28-###-#### 30 min prior to Final Insp start please.
Thank YOU Phone #: ###-#### Inspection requested via web by Teri Cruickshank
|
FIR17-00471
| INSP-Final Inspection | 6/22/2018 | 6/25/2018 | 6/25/2018 3:10:57 PM | P | FAIL |
|
|
Sounder bases in rooms would not stay in alarm during general alarm, sounder bases need to keep sounding during general alarm.
Travis Phone #: ###-####
|
FIR18-00327
| INSP-Sprinkler Rough-in | 6/25/2018 | 6/25/2018 | 6/25/2018 1:51:15 PM | P | PASS |
|
|
New over-build on the southeast side of building has been filled with insulation, no fire sprinkler upright protection required in area filled with insualtion.
Please call Todd 30 minutes prior to arrival Phone #: ###-#### Inspection requested via web by Sam Ball
|
NAF16-00069
| INSP-Sprinkler Rough-in/Hydro | 6/25/2018 | 6/25/2018 | 6/25/2018 1:31:01 PM | P | CANC |
|
|
Call prior to going Phone #: 2087133422 >> Inspection requested via mobile web by Tim Opp Inspection cancelled via mobile web on Monday, June 25, 2018.
|
FIR18-00437
| INSP-Final Inspection | 6/22/2018 | 6/25/2018 | 6/25/2018 11:08:20 AM | A | PASS |
|
|
Final fire sprinkler inspection for area of work complete,
Payton Phone #: ###-####
|
NAF18-00061
| INSP-Sprinkler Rough-in | 6/22/2018 | 6/25/2018 | 6/25/2018 10:38:57 AM | A | FAIL |
|
|
Tenting not installed at time of inspetion, tenitng will need to be completed and inspected before overhead fire sprinkler piping can be covered, no cover is approved.
tenting inspection Phone #: ###-#### Inspection requested via web by Matthew Lewis
|
FIR18-00487
| INSP-Sprinkler Rough-in | 6/25/2018 | 6/25/2018 | 6/25/2018 10:19:44 AM | A | PASS |
|
|
Wrong inspection request was scheduled on 22JUNE2018, inspection should have been a rough in inspection and not a final, permit status has been corrected, notes for rough in inspection are as followed: Rough to cover inspection overhead fire sprinkler piping in area of work complete, approved for cover. Reliable fusible link heads with the 401 escutcheons will need to be changed to quick response heads before final inspection, head change will be verified at final inspection.
|
FIR17-00286
| INSP-Final Inspection | 6/22/2018 | 6/25/2018 | 6/25/2018 10:07:09 AM | A | PASS |
|
|
Final fire sprinkler inspection for area of work complete.
don forester Phone #: ###-#### Inspection requested via web by Brodie Stenquist
|
BLD18-00028
| FIRE-Final Inspection | 6/24/2018 | 6/25/2018 | 6/25/2018 9:37:12 AM | A | PASS |
|
|
Fire sprinkler inspection is complete, fire alarm inspection is complete, fire extinguisher is in place with a current inspection tag, thumbturn deadbolts on south exit doors to be replaced with blanks before final BLD inspection, addressing will be installed when cracked front window is replaced. Final life fire safety inspection complete.
To coincide with alarm and sprinkler finals, as per their permit inspections. Phone #: ###-#### Inspection requested via web by Ryan Wilhelm
|
FIR18-00212
| INSP-Final Inspection | 6/22/2018 | 6/25/2018 | 6/25/2018 9:33:54 AM | A | PASS |
|
|
Final fire alarm inspection for area of work complete.
Contact is Dirk. Phone #: ###-#### Inspection requested via web by Morgan Ahten
|
FIR18-00299
| INSP-Final Inspection | 6/25/2018 | 6/25/2018 | 6/25/2018 9:33:24 AM | A | PASS |
|
|
Final fire sprinkler inspection for area of work complete.
|
BLD18-00736
| FIRE-Final Inspection | 6/25/2018 | 6/25/2018 | 6/25/2018 8:43:04 AM | A | PASS |
|
|
Fire sprinkler inspection complete, fire alarm inspection complete, fire extinguishers are in place with current inspection tags. Final life fire safety inspection for area of work complete.
|
FIR18-00316
| INSP-Final Inspection | 6/22/2018 | 6/25/2018 | 6/25/2018 8:35:45 AM | A | PASS |
|
|
Final fire sprinkler inspection for area of work complete.
Phone #: ###-#### Inspection requested via web by Sam Ball
|
FIR18-00421
| INSP-Final Inspection | 6/22/2018 | 6/25/2018 | 6/25/2018 8:34:45 AM | A | PASS |
|
|
Final fire alarm nispection for area of work complete.
We would like to do the inspection at 7:00 am if possible. Phone #: ###-#### Inspection requested via web by Sam Ball
|
NAF16-00066
| INSP-Final | 6/25/2018 | 6/25/2018 | 6/25/2018 12:00:00 AM | P | PASS |
|
|
Verified that addess has been up dated with the fire department. Ron Johnson verified that he has recieved the update. 6-25-18**ajs**>> Inspection requested via mobile web by ParkwayCall prior to going Phone #: 2087133422 >> Inspection requested via mobile web by Tim opp
|