Inspections for the day of: Tuesday, June 25, 2019.
Number of inspections: 7
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorRock A. Hudson
TitleELE-INSPECTOR
Phone #794-6794
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
ELE19-01213 Final6/24/20196/25/20196/25/2019 2:34:08 PMAPASS
no underground work done. Only wire SC disconnect top. Install single pin disconnect. Code for access is 2914. Call Jason(above number) if further information is needed please. Phone #: ###-#### Inspection requested via web by Sherry Allen
Underground in question was performed by track utitlies company who is exempt from permitting with the city. Steve (###-####) with Idaho Power contruction provided billing report that included photos of underground to base of pole. Final ok
ELE19-00651 Final6/24/20196/25/20196/25/2019 2:07:36 PMPPASS
garage code 0555 Phone #: ###-#### Inspection requested via web by Jay Hutchison Final ok
ELE19-00588 Final6/24/20196/25/20196/25/2019 1:31:43 PMAPASS
Homeowner will be there. Call with any questions Phone #: ###-#### Inspection requested via web by Dylan Pierce
Final ok
ELE19-02149 Final6/24/20196/25/20196/25/2019 11:34:46 AMAPASS
Install complete per approved plans; the stamped and approved plans are on site;
For any questions about the work done for this project, call Jed at ###-####; For any questions about the plans or design, call Ryan at ###-####; thanks guys

the solar disconnect and the panel are all exterior, in front yard, so you can show up any time. The homeowner will be at work but everything is accessible for ya
Phone #: ###-#### Inspection requested via web by Ryan King Final ok
ELE19-00780 Final6/24/20196/25/20196/25/2019 11:07:35 AMAPASS
There will be someone home. If you have any questions please feel free to contact Darren ###-####. Thanks!! Phone #: ###-#### Inspection requested via web by Clayton Morgan Final ok
ELE19-02354 Rough-In Permanent Service6/24/20196/25/20196/25/2019 10:40:45 AMAFAIL
Phone #: ###-#### Inspection requested via web by Neal Rumsey
110.3- Recessed can junction box covers shall be completely installed as per instructions. Kitchen, master bed, pinched wire in up bed.
250.148- Epuipment grounding conductors shall be bonded to metal boxes. net panels.
300.4- Nail plate SER at upper wall in basement.
300.15- NM cables shall terminate in a box. Dining box not stuffed.
314.17- KO seal needed for unused hole in service panel.
314 20- All boxes shall have covers. Recessed coan cover missing in up bathroom.
334.30- NM cable shall be secured with in 12" of 2 gang in down bed.
408.7- Unused breaker spaces shall be closed by approved means. Service panel.
590.6(B)- Receptacles other than 120 volt used for construction shall have GFCI protection. Temp pole 250 will not trip.
ELE19-01330 Final6/24/20196/25/20196/25/2019 9:18:25 AMAPASS
Garage code 1957e Phone #: ###-#### Inspection requested via web by Alan Lusk
Final ok