Inspections for the day of: Wednesday, June 26, 2002.
Number of inspections: 14
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorJack Frank
TitleELE-INSPECTOR
Phone #794-1930
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
ELE02-01915 Electrical Rough-In6/25/20026/26/20026/26/2002 12:00:00 AMAFAIL
r/i- please call 1st before insp/###-#### marv
met with contractor correction posted 300.10 shall install bond bushings where conduits enter non metallic boxes and R E washers are used 314.15 shall install hubs, sealing locknut, or washers for wet location(car wash) 6/26/2002 11:08:59 AM
ELE02-00523 Rough-In Permanent Service6/25/20026/26/20026/26/2002 12:00:00 AMAPASS
###-#### MIKE r/i in garage and house ok needs clearence for sub panel in basement

p/s o/h rec ok 6/26/2002 12:00:07 PM
ELE02-01925 Temporary Service6/25/20026/26/20026/26/2002 12:00:00 AMAPASS
repuested by jack.

t/s u/g new ok 6/25/2002 6:30:15 PM
ELE02-01938 Temporary Service6/25/20026/26/20026/26/2002 12:00:00 AMAFAIL
karen ###-#### called needs 220 volt gfci breaker 6/26/2002 1:51:43 PM
ELE01-04209 Final6/25/20026/26/20026/26/2002 12:00:00 AMAPART
JOCK ###-#### partial only owner still has a few things to do for complete final 6/26/2002 3:03:11 PM
ELE02-01932 Electrical Rough-In6/25/20026/26/20026/26/2002 12:00:00 AMANH
Scheduled by a contractor via Hello! on 06/25/2002 at 15:30:26. Contact: ###-####. called no access all corrections not made 6/26/2002 10:40:06 AM
ELE02-01431 Final6/25/20026/26/20026/26/2002 12:00:00 AMAPASS
Scheduled by a contractor via Hello! on 06/25/2002 at 22:53:56. Contact: ###-####. ok 6/26/2002 10:17:02 AM
ELE02-01290 Electrical Rough-In6/26/20026/26/20026/26/2002 12:00:00 AMAPASS
Scheduled by a contractor via Hello! on 06/26/2002 at 07:17:46. Contact: ###-####. ok 6/26/2002 12:31:23 PM
ELE02-01940 Rough-In Permanent Service6/26/20026/26/20026/26/2002 12:00:00 AMPPART
JOHN ###-#### PLEASE CALL JOHN AS THIS IS IN ST ALS SOUTH TOWER... conference only ok 6/26/2002 5:07:27 PM
ELE02-01832 Electrical Rough-In6/26/20026/26/20026/26/2002 12:00:00 AMPFAIL
call 1st before insp- nolan- ###-#### cell
cor. posted met contractor at job site not ready, and 314.20 boxes set back more than 1/4 inch from combustible finished surface 6/26/2002 3:39:57 PM
ELE02-01796 Final6/26/20026/26/20026/26/2002 12:00:00 AMPPASS
fn - miller elec-###-#### ok 6/26/2002 5:23:33 PM
ELE02-01950 Electrical Rough-In6/26/20026/26/20026/26/2002 12:00:00 AMPPART
John ###-#### u/g and floor boxes only no walls 6/26/2002 3:54:20 PM
ELE02-01405 Final6/25/20026/26/20026/26/2002 12:00:00 AMPPASS
Scheduled by a contractor via Hello! on 06/25/2002 at 15:11:28. Contact: ###-####. ok
6/26/2002 5:51:01 PM
ELE02-01802 Permanent Service6/14/20026/26/20026/26/2002 12:00:00 AMPCANC
dale ###-####--cancel per jeff