Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
FIR02-00202 INSP-Sprinkler Rough-in6/25/20026/26/20026/26/2002 12:00:00 AMAFAIL
mattresses must be stored below 12', product cannot be encapsulated, replace solid shelving with open shelving, maintain flu space behind the racking, maintain 6" min. clearance between sprinkler head and the top of the product, provide EQ at top of the 4" drop downs to the rack sprinklers or provide verification of non requirement, move EQ attachments to the top of the truss instead of the bottom or provide verification per NFPA 13. 6/26/2002 10:41:13 AM
BLD99-00444 FIRE-Final Inspection6/25/20026/26/20026/26/2002 12:00:00 AMPFAIL
remove thumbturns on the exterior doors, provide approved hardware for the second floor offices 6/26/2002 1:30:55 PM