ELE06-01689
| Final | 6/26/2006 | 6/26/2006 | 6/26/2006 4:20:24 PM | P | PASS |
|
|
dino - call for access; Phone #: ###-#### Internet Inspection Request from: Barbara Buckley called contr to chg ac bkr to 30A and firmly mount front and rear rcpt, ok to final
|
ELE06-00671
| Electrical Rough-In | 6/26/2006 | 6/26/2006 | 6/26/2006 3:54:45 PM | P | PART |
|
|
tye Note: underground; Phone #: ###-#### Internet Inspection Request from: Cathy Chiles ok to cover north wall area for conduit and gec (south wall mcc area)
|
ELE06-02368
| Temporary Service | 6/26/2006 | 6/26/2006 | 6/26/2006 3:36:11 PM | P | PASS |
|
|
###-#### - bernice t/s u/g n ok
|
ELE05-03277
| Final | 6/26/2006 | 6/26/2006 | 6/26/2006 2:35:21 PM | P | PART |
|
|
Scheduled by a contractor via Hello! on 6/26/2006 at 7:43:00 AM. Contact: ###-####. called, left corr notice, nec 410.21 equipment shall be mechanically connected to equipment grounding conductor (poles), 406.5 recpt faceplates shall be installed, BCC permanent address shall be posted,shall have interior access
|
ELE05-03276
| Final | 6/26/2006 | 6/26/2006 | 6/26/2006 2:03:33 PM | P | PART |
|
|
Scheduled by a contractor via Hello! on 6/26/2006 at 7:41:28 AM. Contact: ###-####. called, left corr notice, nec 410.21 equipment shall be mechanically connected to equipment grounding conductor (poles), 406.5 receptacle faceplates shall be installed,BCC permanent address shall be posted, shall have interior access
|
ELE06-01688
| Final | 6/26/2006 | 6/26/2006 | 6/26/2006 1:20:36 PM | P | PASS |
|
|
dino - call for access; Phone #: ###-#### Internet Inspection Request from: Barbara Buckley ok to final
|
ELE06-02174
| Final | 6/23/2006 | 6/26/2006 | 6/26/2006 11:43:12 AM | A | PASS |
|
|
Butch; Phone #: ###-#### Internet Inspection Request from: Rita DeYoung ok to final
|
ELE06-02361
| Temporary Service | 6/23/2006 | 6/26/2006 | 6/26/2006 9:51:23 AM | A | PASS |
|
|
emmet; Phone #: ###-#### Internet Inspection Request from: Barbara Buckley called, left survey, 312.5 abrasion protection shall be provided for all conductors entering enclosures
|
ELE06-01834
| Rough-In Permanent Service | 6/22/2006 | 6/26/2006 | 6/26/2006 9:37:44 AM | A | FAIL |
|
|
Darrin; Phone #: ###-#### Internet Inspection Request from: Cathy Weisshaupt corrections not made, said to call when done
|
ELE06-01394
| Final | 6/24/2006 | 6/26/2006 | 6/26/2006 9:31:11 AM | A | FAIL |
|
|
Malai Thai Spa monument sign behind Cole School; Phone #: ###-#### Internet Inspection Request from: Eric Shaner called, left corr notice, nec 400.14 flexible cords and cables shall be protected by bushings or fittings where passing through holes in covers, BCC 4-05-33(A)(B) equipment shall be listed and labelled by a nationally recognized testing lab
|
ELE06-02350
| Final | 6/23/2006 | 6/26/2006 | 6/26/2006 9:04:09 AM | A | NH |
|
|
Please call ###-#### for building access.; Phone #: ###-#### Internet Inspection Request from: Tawnya McKinney called, said to call when can access
|
ELE06-02042
| Final | 6/25/2006 | 6/26/2006 | 6/26/2006 8:45:20 AM | A | PASS |
|
|
We need to modify the permit for 5 rooms and a jet tub, this was not entered correctly upon rough in. Please call if I need to take care of this via phone.; Phone #: ###-#### Internet Inspection Request from: Monty Adkinson ok to final
|
ELE06-02305
| Final | 6/26/2006 | 6/26/2006 | 6/26/2006 8:17:12 AM | A | CANC |
|
|
Phone #: ###-#### Internet Inspection Request from: Jim Williams see t/s
|
ELE06-02305
| Temporary Service | 6/26/2006 | 6/26/2006 | 6/26/2006 8:16:49 AM | A | PASS |
|
|
Phone #: ###-#### Internet Inspection Request from: Jim Williams corr made, t/s u/g n ok
|