Inspections for the day of: Monday, June 26, 2006.
Number of inspections: 14
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorBob Reichert
TitleELE-INSPECTOR
Phone #794-1923
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
ELE06-01689 Final6/26/20066/26/20066/26/2006 4:20:24 PMPPASS
dino - call for access; Phone #: ###-#### Internet Inspection Request from: Barbara Buckley called contr to chg ac bkr to 30A and firmly mount front and rear rcpt, ok to final
ELE06-00671 Electrical Rough-In6/26/20066/26/20066/26/2006 3:54:45 PMPPART
tye Note: underground; Phone #: ###-#### Internet Inspection Request from: Cathy Chiles ok to cover north wall area for conduit and gec (south wall mcc area)
ELE06-02368 Temporary Service6/26/20066/26/20066/26/2006 3:36:11 PMPPASS
###-#### - bernice t/s u/g n ok
ELE05-03277 Final6/26/20066/26/20066/26/2006 2:35:21 PMPPART
Scheduled by a contractor via Hello! on 6/26/2006 at 7:43:00 AM. Contact: ###-####. called, left corr notice, nec 410.21 equipment shall be mechanically connected to equipment grounding conductor (poles), 406.5 recpt faceplates shall be installed, BCC permanent address shall be posted,shall have interior access
ELE05-03276 Final6/26/20066/26/20066/26/2006 2:03:33 PMPPART
Scheduled by a contractor via Hello! on 6/26/2006 at 7:41:28 AM. Contact: ###-####. called, left corr notice, nec 410.21 equipment shall be mechanically connected to equipment grounding conductor (poles), 406.5 receptacle faceplates shall be installed,BCC permanent address shall be posted, shall have interior access
ELE06-01688 Final6/26/20066/26/20066/26/2006 1:20:36 PMPPASS
dino - call for access; Phone #: ###-#### Internet Inspection Request from: Barbara Buckley ok to final
ELE06-02174 Final6/23/20066/26/20066/26/2006 11:43:12 AMAPASS
Butch; Phone #: ###-#### Internet Inspection Request from: Rita DeYoung ok to final
ELE06-02361 Temporary Service6/23/20066/26/20066/26/2006 9:51:23 AMAPASS
emmet; Phone #: ###-#### Internet Inspection Request from: Barbara Buckley called, left survey, 312.5 abrasion protection shall be provided for all conductors entering enclosures
ELE06-01834 Rough-In Permanent Service6/22/20066/26/20066/26/2006 9:37:44 AMAFAIL
Darrin; Phone #: ###-#### Internet Inspection Request from: Cathy Weisshaupt corrections not made, said to call when done
ELE06-01394 Final6/24/20066/26/20066/26/2006 9:31:11 AMAFAIL
Malai Thai Spa monument sign behind Cole School; Phone #: ###-#### Internet Inspection Request from: Eric Shaner called, left corr notice, nec 400.14 flexible cords and cables shall be protected by bushings or fittings where passing through holes in covers, BCC 4-05-33(A)(B) equipment shall be listed and labelled by a nationally recognized testing lab
ELE06-02350 Final6/23/20066/26/20066/26/2006 9:04:09 AMANH
Please call ###-#### for building access.; Phone #: ###-#### Internet Inspection Request from: Tawnya McKinney called, said to call when can access
ELE06-02042 Final6/25/20066/26/20066/26/2006 8:45:20 AMAPASS
We need to modify the permit for 5 rooms and a jet tub, this was not entered correctly upon rough in. Please call if I need to take care of this via phone.; Phone #: ###-#### Internet Inspection Request from: Monty Adkinson ok to final
ELE06-02305 Final6/26/20066/26/20066/26/2006 8:17:12 AMACANC
Phone #: ###-#### Internet Inspection Request from: Jim Williams see t/s
ELE06-02305 Temporary Service6/26/20066/26/20066/26/2006 8:16:49 AMAPASS
Phone #: ###-#### Internet Inspection Request from: Jim Williams corr made, t/s u/g n ok