Inspections for the day of: Monday, June 26, 2006.
Number of inspections: 11
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorForrest France
TitleFIRE INSPECTOR
Phone #794-1981
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
FIR05-00631 INSP-Final Inspection6/26/20066/26/20066/27/2006 1:53:17 PMPFAIL
Need to replace one defective SW head at the garage area, repair leaking main drain connection, provide spare SW in head box.
FIR06-00110 INSP-Final Inspection6/20/20066/26/20066/26/2006 4:16:02 PMPPASS
Fire alarm work is satisfactory, inspection passed.
FIR06-00063 INSP-Sprinkler Rough-in/Hydro6/20/20066/26/20066/26/2006 3:50:54 PMPPART
Overhead rough-in for phase one of the project as marked on approved plans is okay to cover.
FIR05-00713 INSP-Sprinkler Rough-in/Hydro6/26/20066/26/20066/26/2006 2:44:22 PMPFAIL
Visible leakage at three locations observed on the overhead system during hydrostatic test.
FIR05-00321 FIR-Aging Inspection6/26/20066/26/20066/26/2006 1:53:33 PM DONE
Spoke to George with General Fire about an inspection request to final this permit.
FIR06-00018 INSP-Final Inspection6/23/20066/26/20066/26/2006 1:52:31 PMAPASS
Hood suppression system functioned properly under test conditions, inspection passed.
FIR06-00212 INSP-Final Inspection6/26/20066/26/20066/26/2006 1:24:38 PMPFAIL
Door to the remodeled area was locked, no access provided, spoke with contractor to reschedule inspection.
BLD06-01341 FIRE-Final Inspection6/23/20066/26/20066/26/2006 12:24:10 PMAFAIL
Need to provide correct suite address, mount fire extinguisher as discussed, door stoppers at the main entry/exit doors to the suite shall be removed. NOTE: The tenant has occupied the space and is conducting business without and prior to occupancy certificate approval, general contractor is aware of the situation.
FIR06-00458 INSP-Final Inspection6/23/20066/26/20066/26/2006 12:19:40 PMAPASS
Wattage at one a/v increased to meet audibility requirements, alarm work is satisfactory, permit finaled.
BLD06-00055 FIRE-Final Inspection6/23/20066/26/20066/26/2006 11:08:17 AMAPASS
Fire life safety for the new kitchen area is acceptable.
BLD06-00514 FIRE-Final Inspection6/26/20066/26/20066/26/2006 10:35:13 AMAPASS
c/n items verified, inspection passed