Inspections for the day of: Tuesday, June 26, 2007.
Number of inspections: 11
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorJack Frank
TitleELE-INSPECTOR
Phone #794-1930
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
ELE07-02005 Final6/25/20076/26/20076/26/2007 3:24:38 PMPFAIL
Scheduled by a contractor via Hello! on 6/25/2007 at 9:39:31 PM. Contact: ###-####. no pwer for new p/s can't do a final without power c alled
ELE07-02005 Permanent Service6/25/20076/26/20076/26/2007 3:22:25 PMPFAIL
Scheduled by a contractor via Hello! on 6/25/2007 at 9:38:46 PM. Contact: ###-####. called corr 250.92(A)(3) needs bonding both ends of conduit for GEC, shall terminate GEC to old GEC buse or tap to it, install bond strap at new 200 amp P/S needs labels noting both disconnects for tennant
ELE07-02043 Permanent Service6/26/20076/26/20076/26/2007 2:40:00 PMPFAIL
steve Phone #: ###-#### corr 250.64(E) and 110.26(F)(2) shall use conn listed for grding for GEC
ELE07-01613 Rough-In Permanent Service6/26/20076/26/20076/26/2007 2:18:50 PMPPART
Gene - ###-####. Thank you!! Phone #: ###-#### Internet Inspection Request from: Tracy Robertson r/i only ok needs clearence in front of p/s 110.26(F)(2) called
ELE07-02293 Final6/26/20076/26/20076/26/2007 1:37:27 PMPPART
Pat Gill ###-#### Phone #: ###-#### Internet Inspection Request from: Debby Ellis no final needs p/s conference only ok for service damaged by road work crew
ELE07-01438 Electrical Rough-In6/26/20076/26/20076/26/2007 12:55:04 PMPFAIL
Scheduled by a contractor via Hello! on 6/26/2007 at 8:52:26 AM. Contact: ###-####. called rebar not install per NEC 680.26 (C) and electical newws brief do not cover posted, 12" squares and shall start from edgwe of pool 3 ft out no gaps allowed
ELE07-01808 Final6/25/20076/26/20076/26/2007 11:10:16 AMAPASS
Equal potential & final Phone #: ###-#### Internet Inspection Request from: Jari Rivers ok new pool called about switch where off is on and on is off pool guy has valve backwards
ELE07-02279 Final6/25/20076/26/20076/26/2007 10:41:32 AMACANC
andy Phone #: ###-#### called contr will reschedule as r/i and provide access
ELE07-01364 Final6/25/20076/26/20076/26/2007 10:35:56 AMAPASS
chris Phone #: ###-#### ok card signed
ELE07-01715 Final6/25/20076/26/20076/26/2007 10:05:11 AMAPASS
LLOYD Phone #: ###-#### ok
ELE06-02704 Final6/25/20076/26/20076/26/2007 9:38:12 AMAPART
Please inspect C-wing all floors for final. Phone #: ###-#### Internet Inspection Request from: Jim all of 1st floor 1/2 of 2nd floor no finan needs enclosed fixtures and clearence closet lights, and bond isolated water pipes each wing at W H room