Inspections for the day of: Tuesday, June 26, 2007.
Number of inspections: 13
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorForrest France
TitleFIRE INSPECTOR
Phone #794-1981
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
FIR07-00087 FIR-Aging Inspection6/26/20076/26/20076/27/2007 10:15:27 AM DONE
Tenant work in progress.
FIR07-00205 INSP-Sprinkler Rough-in6/25/20076/26/20076/26/2007 5:02:14 PMPFAIL
Inspected OH rough-in for the 2nd level areas A and B sheets FP5 and 6, noted on plans defficient areas with missing heads, overspaced heads, hangers, retaining straps, areas not yet complete etc., flex heads in the cleanroom are not completed at this time.
FIR06-00940 INSP-Sprinkler Rough-in6/25/20076/26/20076/26/2007 4:39:51 PMPPART
Verified corrections have been made for the basement level piping, noted two stair enclosures are not yet piped, some upright heads in the corridor may become blocked due to excessive amounts of mechanical and electrical equipment in process of installation below the heads.
FIR07-00453 INSP-Final Inspection6/22/20076/26/20076/26/2007 4:35:35 PMPNR
Permit work is not completed for final at this time.
FIR07-00453 INSP-Sprinkler Rough-in6/22/20076/26/20076/26/2007 4:34:42 PMPPART
Some items noted at previous inspection including added heads in the lobby restroom, relocated heads at the 2nd floor conference room have been completed. Remaining items include missing heads at the cash and vault rooms, missing escutcheons, one head at the teller lobby to be replaced, covered heads at the 1st floor west stair landing, still need final for the shell and core permit.
FIR06-00615 INSP-Sprinkler Rough-in/Hydro6/25/20076/26/20076/26/2007 1:36:30 PMAPASS
Fire sprinkler system modifications passed inspection.
FIR07-00543 INSP-Sprinkler Rough-in6/25/20076/26/20076/26/2007 12:13:19 PMAPART
OH fire sprinkler modifications are approved for cover at the drop ceilings, final pending ceiling tile and escutcheons.
BLD06-03574 FIRE-Final Inspection6/26/20076/26/20076/26/2007 11:46:03 AMPNR
Building life safety final pending project related fire sprinkler permit final, one emergency light has been repaired.
FIR07-00311 INSP-Final Inspection6/26/20076/26/20076/26/2007 11:44:16 AMPFAIL
Previously noted pendent head in the storage room is still not correctly installed.
FIR07-00358 INSP-Final Inspection6/26/20076/26/20076/26/2007 11:35:45 AMPPASS
Fire alarm permit finaled.
BLD06-01651 FIRE-Final Inspection6/26/20076/26/20076/26/2007 11:13:06 AMPPART
Inspection for units 208, 209, 210, 211 on the west end of the building completed satisfactory, plastic cover and battery lid replaced on two SD while on site, noted the basement level storage areas will require smoke detectors and at least one fire extinguisher- see plan review notes and annotations, the remaining 8 units in this building are not yet completed for final.
BLD06-02542 FIRE-Final Inspection6/25/20076/26/20076/26/2007 11:05:29 AMANR
Wrong project permit number called in, this building is not yet ready for final inspection, was intended for the adjacent structure.
FIR07-00358 INSP-Alarm Testing6/25/20076/26/20076/26/2007 10:09:53 AMAPASS
Corrections completed, fire alarm testing passed.