Inspections for the day of: Tuesday, June 26, 2007.
Number of inspections: 11
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorTroy Cobbley
TitleFIRE INSPECTOR
Phone #794-9483
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
FIR06-00958 INSP-Sprinkler Rough-in6/25/20076/26/20076/27/2007 11:02:48 AMPCANC
This part of the project was not ready for inspection.
FIR06-00957 INSP-Sprinkler Rough-in6/25/20076/26/20076/27/2007 11:02:13 AMPPASS
I inspected Bldg. D attic piping today. There were a few problems with bracing, the problems were corrected by the end of the inspection. I also witnessed the hydro test for the attic piping and second floor of the same bldg. The hydro went fine.
FIR07-00541 INSP-Final Inspection6/25/20076/26/20076/27/2007 10:07:27 AMAPASS
Permit finaled. The phone lines connected to the D928 dialer had been connected wrong. Dan and I worked with tech support to figure it out.
BLD07-00746 FIRE-Final Inspection6/25/20076/26/20076/26/2007 3:07:54 PMAFAIL
Mount the fire extinguishers as discussed and provide the missing exit discharge light or provide revised plans to the city of boise and provide justification for the deletion of the lights.
FIR07-00097 INSP-Final Inspection6/26/20076/26/20076/26/2007 1:50:47 PMPFAIL
The plans show 1 1/4 pipe but 1 is installed
FIR07-00492 INSP-Final Inspection6/26/20076/26/20076/26/2007 1:39:53 PMPPASS
permit finaled.
MIS07-00141 FIR-Final6/26/20076/26/20076/26/2007 1:05:09 PMPFAIL
Sprinkler pendants are overspaced and provide a fire extinguisher as discussed.
FIR07-00445 INSP-Final Inspection6/25/20076/26/20076/26/2007 12:36:56 PMPPASS
permit finaled.
FIR07-00423 INSP-Final Inspection6/25/20076/26/20076/26/2007 10:50:45 AMPPASS
permit finaled.
FIR07-00431 INSP-Sprinkler Rough-in6/25/20076/26/20076/26/2007 9:57:10 AMAPASS
Sprinkler piping is ok to cover. Noted that the small electrical closet will need a ceiling or the upright sprinkler protection will need to be re-installed.
FIR06-00367 INSP-Final Inspection6/21/20076/26/20076/26/2007 8:04:25 AMAFAIL
The only item that tested ok was the duct smoke detector in the Lucent tenant space. The plans need to be resubmitted showing the slave radionics dialer that has been connected to the Simplex 4005 panel. The dialer is not sending out phone line troubles or loss of battery. It did however send out the duct detector supervisory and the loss of ac power. A building map needs to be provided and the power supply for the dialer needs to be mechanically secured. No other duct detectors were tested or any of the sprinkler devices. Test has been stopped and failed.