FIR06-00958
| INSP-Sprinkler Rough-in | 6/25/2007 | 6/26/2007 | 6/27/2007 11:02:48 AM | P | CANC |
|
|
This part of the project was not ready for inspection.
|
FIR06-00957
| INSP-Sprinkler Rough-in | 6/25/2007 | 6/26/2007 | 6/27/2007 11:02:13 AM | P | PASS |
|
|
I inspected Bldg. D attic piping today. There were a few problems with bracing, the problems were corrected by the end of the inspection. I also witnessed the hydro test for the attic piping and second floor of the same bldg. The hydro went fine.
|
FIR07-00541
| INSP-Final Inspection | 6/25/2007 | 6/26/2007 | 6/27/2007 10:07:27 AM | A | PASS |
|
|
Permit finaled. The phone lines connected to the D928 dialer had been connected wrong. Dan and I worked with tech support to figure it out.
|
BLD07-00746
| FIRE-Final Inspection | 6/25/2007 | 6/26/2007 | 6/26/2007 3:07:54 PM | A | FAIL |
|
|
Mount the fire extinguishers as discussed and provide the missing exit discharge light or provide revised plans to the city of boise and provide justification for the deletion of the lights.
|
FIR07-00097
| INSP-Final Inspection | 6/26/2007 | 6/26/2007 | 6/26/2007 1:50:47 PM | P | FAIL |
|
|
The plans show 1 1/4 pipe but 1 is installed
|
FIR07-00492
| INSP-Final Inspection | 6/26/2007 | 6/26/2007 | 6/26/2007 1:39:53 PM | P | PASS |
|
|
permit finaled.
|
MIS07-00141
| FIR-Final | 6/26/2007 | 6/26/2007 | 6/26/2007 1:05:09 PM | P | FAIL |
|
|
Sprinkler pendants are overspaced and provide a fire extinguisher as discussed.
|
FIR07-00445
| INSP-Final Inspection | 6/25/2007 | 6/26/2007 | 6/26/2007 12:36:56 PM | P | PASS |
|
|
permit finaled.
|
FIR07-00423
| INSP-Final Inspection | 6/25/2007 | 6/26/2007 | 6/26/2007 10:50:45 AM | P | PASS |
|
|
permit finaled.
|
FIR07-00431
| INSP-Sprinkler Rough-in | 6/25/2007 | 6/26/2007 | 6/26/2007 9:57:10 AM | A | PASS |
|
|
Sprinkler piping is ok to cover. Noted that the small electrical closet will need a ceiling or the upright sprinkler protection will need to be re-installed.
|
FIR06-00367
| INSP-Final Inspection | 6/21/2007 | 6/26/2007 | 6/26/2007 8:04:25 AM | A | FAIL |
|
|
The only item that tested ok was the duct smoke detector in the Lucent tenant space. The plans need to be resubmitted showing the slave radionics dialer that has been connected to the Simplex 4005 panel. The dialer is not sending out phone line troubles or loss of battery. It did however send out the duct detector supervisory and the loss of ac power. A building map needs to be provided and the power supply for the dialer needs to be mechanically secured. No other duct detectors were tested or any of the sprinkler devices. Test has been stopped and failed.
|