Inspections for the day of: Tuesday, June 26, 2012.
Number of inspections: 9
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorForrest France
TitleFIRE INSPECTOR
Phone #794-1981
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
FIR12-00189 INSP-Final Inspection6/25/20126/26/20126/26/2012 4:01:57 PMPPART
Overhead rough-in passed.
FIR12-00189 INSP-Sprinkler Rough-in/Hydro6/25/20126/26/20126/26/2012 4:00:13 PMPPART
Overhead hydrostatic test completed.
BLD12-00508 FIRE-Final Inspection6/26/20126/26/20126/26/2012 3:59:33 PMPNR
Fire alarm permit final pending, noted missing building address numbers.
BLD12-00730 FIRE-Final Inspection6/26/20126/26/20126/26/2012 3:57:43 PMPPEND
Pending fire alarm permit final.
FIR11-00351 INSP-Conference6/26/20126/26/20126/26/2012 3:56:53 PMPDONE
FIR12-00146 INSP-Final Inspection6/25/20126/26/20126/26/2012 3:56:30 PMAPART
Completed new system acceptance testing. Final pending as-built plans to include revised location of the FACP, SD, and MP, post signage at the door to the control panel room, provide points map at the panel. Tenant has requested alternate proposals to the system design in order to reduce possibility of false alarms due to environmental conditions at the truck repair bays.
BLD11-01555 FIRE-Final Inspection6/25/20126/26/20126/26/2012 3:47:22 PMAPASS
Fire life safety inspection passed.
FIR12-00145 INSP-Final Inspection6/22/20126/26/20126/26/2012 3:46:48 PMAPASS
Fire alarm work passed acceptance testing after adjustments made while on site. Permit finaled.
FIR12-00041 INSP-Final Inspection6/26/20126/26/20126/26/2012 3:44:48 PMAPASS
Fire sprinkler permit work passed final inspection and walkthrough.