Inspections for the day of: Friday, June 26, 2015.
Number of inspections: 4
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorThomas Walsh
TitleFIRE INSPECTOR
Phone #794-1981
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
FIR14-00792 INSP-Sprinkler Rough-in6/26/20156/26/20156/26/2015 3:47:24 PMPPART
RTC inspection for Bldg H wet system for first and second floors - hard lid areas - see plans for areas inspected. Also Bldg H first floor feed main provides protection for the bulk feed main that supplies wings A-D, that are completed and in service.
FIR14-00071 INSP-Sprinkler Rough-in/Hydro6/26/20156/26/20156/26/2015 3:43:43 PMPPASS
Bldg L dry pipe system hydrotest (200 psi @ 2 hours) - PASSED
FIR15-00096 INSP-Sprinkler Rough-in/Hydro6/25/20156/26/20156/26/2015 3:41:48 PMAPART
RTC inspection for dry and wet pipe system supplying the noth side of floor #5. Both passed inspection, while some repair work was needed for several draft stops, that were repaired before the end of the inspection. OK to cover for these two systems. Also tenting (insulation) inspection of units 509, 510, 512, 513, 514, 515, 516, 517 and 518.
FIR14-00687 INSP-Sprinkler Rough-in6/25/20156/26/20156/26/2015 3:37:48 PMACANC
Wrong permit for this day's inspection. See FIR14-00096 for inspections completed today (6/26).