ELE17-00682
| Final | 6/26/2017 | 6/26/2017 | 6/26/2017 2:39:11 PM | P | FAIL |
|
|
Contact: Matt Cinko.... Call 30 minutes before going so Matt can meet and let you in please Phone #: ###-#### Inspection requested via web by Deb Gooden 210.8- 120 volt 15 or 20 amp receptacle outlets located with in 6' of a sink or basin shall have GFCI protection. 300.15- All boxes nad devices shall have covers installed at time of inspection. 408.4- Circuit directory shall be complete.
|
ELE16-01946
| Final | 6/26/2017 | 6/26/2017 | 6/26/2017 2:09:21 PM | P | PASS |
|
|
Phone #: ###-#### Inspection requested via web by Kerri Hamilton Final ok
|
ELE16-01667
| Electrical Rough-In | 6/26/2017 | 6/26/2017 | 6/26/2017 1:33:19 PM | P | PASS |
|
|
Drop ceilings 211 , 212 Phone #: ###-#### Inspection requested via web by Tom Betty Areas noted rough in ok cover
|
ELE17-01569
| Final | 6/25/2017 | 6/26/2017 | 6/26/2017 1:09:07 PM | P | FAIL |
|
|
Sorry had to cancel the AM request and move it to PM we didn''t quite get done Friday, should be ready by after noon thanks Brad Phone #: ###-#### Inspection requested via web by Brad Baker 210.8- All 120 volt 15 or 20 amp receptacle outlets located with in 6' of a sink shall have GFCI protection. 314.30- All boxes shall be secured in place. 330.30 MC shall be secured with in 12" of a box,
|
ELE17-01612
| Final | 6/23/2017 | 6/26/2017 | 6/26/2017 11:08:51 AM | P | CANC |
|
|
Final inspection please. Phone #: ###-#### >> Inspection requested via web by Kyle Lott Inspection cancelled from web by: Kyle Lott
|
ELE17-01964
| Final | 6/26/2017 | 6/26/2017 | 6/26/2017 10:11:53 AM | A | FAIL |
|
|
Work completed on 3 signs, 3rd. sign circuit demoed, no rough in. Phone #: ###-#### Inspection requested via web by Mark M North east corner of hospital sign removed, other 2 previously noted complete except for receptacle installed under signs. 406.9(B)- All receptacles installed in a wet location shall be weather resistant type.
|
ELE17-01366
| Final | 6/25/2017 | 6/26/2017 | 6/26/2017 9:25:28 AM | A | FAIL |
|
|
Phone #: ###-#### Inspection requested via web by Ben Archibald 210.12- AFCI protection required for office with clothes closet. 408.4- Circuit directory shall be accurate. AFCI on living room, office is #24.
|
ELE17-02006
| Electrical Rough-In | 6/26/2017 | 6/26/2017 | 6/26/2017 8:56:58 AM | A | PASS |
|
|
Homeowner will be home until 10am, if after that please call me to insure access. Thank you Shaun ###-#### Phone #: ###-#### Inspection requested via web by Shaun Kirkman Rough in ok cover
|
ELE17-01569
| Final | 6/22/2017 | 6/26/2017 | 6/25/2017 9:31:40 PM | A | CANC |
|
|
Phone #: ###-#### >> Inspection requested via web by Brad Baker Inspection cancelled from web by: Brad Baker
|