Inspections for the day of: Monday, June 26, 2017.
Number of inspections: 9
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorRock A. Hudson
TitleELE-INSPECTOR
Phone #794-6794
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
ELE17-00682 Final6/26/20176/26/20176/26/2017 2:39:11 PMPFAIL
Contact: Matt Cinko.... Call 30 minutes before going so Matt can meet and let you in please Phone #: ###-#### Inspection requested via web by Deb Gooden
210.8- 120 volt 15 or 20 amp receptacle outlets located with in 6' of a sink or basin shall have GFCI protection.
300.15- All boxes nad devices shall have covers installed at time of inspection.
408.4- Circuit directory shall be complete.
ELE16-01946 Final6/26/20176/26/20176/26/2017 2:09:21 PMPPASS
Phone #: ###-#### Inspection requested via web by Kerri Hamilton Final ok
ELE16-01667 Electrical Rough-In6/26/20176/26/20176/26/2017 1:33:19 PMPPASS
Drop ceilings 211 , 212 Phone #: ###-#### Inspection requested via web by Tom Betty Areas noted rough in ok cover
ELE17-01569 Final6/25/20176/26/20176/26/2017 1:09:07 PMPFAIL
Sorry had to cancel the AM request and move it to PM we didn''t quite get done Friday, should be ready by after noon thanks Brad Phone #: ###-#### Inspection requested via web by Brad Baker
210.8- All 120 volt 15 or 20 amp receptacle outlets located with in 6' of a sink shall have GFCI protection.
314.30- All boxes shall be secured in place. 330.30 MC shall be secured with in 12" of a box,
ELE17-01612 Final6/23/20176/26/20176/26/2017 11:08:51 AMPCANC
Final inspection please. Phone #: ###-#### >> Inspection requested via web by Kyle Lott Inspection cancelled from web by: Kyle Lott
ELE17-01964 Final6/26/20176/26/20176/26/2017 10:11:53 AMAFAIL
Work completed on 3 signs, 3rd. sign circuit demoed, no rough in. Phone #: ###-#### Inspection requested via web by Mark M
North east corner of hospital sign removed, other 2 previously noted complete except for receptacle installed under signs.
406.9(B)- All receptacles installed in a wet location shall be weather resistant type.
ELE17-01366 Final6/25/20176/26/20176/26/2017 9:25:28 AMAFAIL
Phone #: ###-#### Inspection requested via web by Ben Archibald
210.12- AFCI protection required for office with clothes closet.
408.4- Circuit directory shall be accurate. AFCI on living room, office is #24.
ELE17-02006 Electrical Rough-In6/26/20176/26/20176/26/2017 8:56:58 AMAPASS
Homeowner will be home until 10am, if after that please call me to insure access. Thank you Shaun ###-#### Phone #: ###-#### Inspection requested via web by Shaun Kirkman
Rough in ok cover
ELE17-01569 Final6/22/20176/26/20176/25/2017 9:31:40 PMACANC
Phone #: ###-#### >> Inspection requested via web by Brad Baker Inspection cancelled from web by: Brad Baker