Inspections for the day of: Tuesday, June 26, 2018.
Number of inspections: 14
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorTom Saunders
TitleELE-INSPECTOR
Phone #208-794-1923
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
ELE18-02181 Electrical Rough-In6/26/20186/26/20186/26/2018 2:38:54 PMPPASS
Uffer Ground Phone #: ###-#### Inspection requested via web by Bryan Atkins...ok to cover
ELE18-01854 Electrical Rough-In6/26/20186/26/20186/26/2018 2:25:17 PMPPASS
Phone #: ###-#### Inspection requested via web by Tom Jenkins...walls and hard lid ok to cover
ELE18-02357 Permanent Service6/26/20186/26/20186/26/2018 2:19:23 PMPPASS
reenergize...p/s o/h reconnect ok

will verify grounding of water pipe at time of final..given wrong size wire at store...no eddison circuits...verify labelling at final
ELE18-02390 Electrical Rough-In6/26/20186/26/20186/26/2018 1:05:55 PMPPASS
underground rough in for bollard lights along walkway running East to West along North side of apartment complex site.
See Ryan
Phone #: ###-#### Inspection requested via web by Todd Hall...ok to cover
ELE18-02339 Conference6/25/20186/26/20186/26/2018 11:32:04 AMAPASS
Call half hour before to meet // Alek Phone #: ###-####...discussed wiring of addition...new service location..power requirement for new addition and existing house...one service drop only...pamphlet given on wiring new addition...homeowner competent to do work
ELE18-02222 Final6/25/20186/26/20186/26/2018 10:20:19 AMAFAIL
Phone #: ###-#### Inspection requested via web by Ashley Rasmussen....Boise City requirement that rough inspection be performed before a final can be scheduled...contractor must be onsite to remove panels and verify UL listing of equipment and proper grounding before a final will be given
ELE18-00715 Final6/25/20186/26/20186/26/2018 10:13:41 AMAFAIL
Phone #: ###-#### Inspection requested via web by Todd Hall...switch in kitchen needs installed completely...plate and recessed flush
ELE18-00716 Final6/25/20186/26/20186/26/2018 10:12:32 AMAPASS
Phone #: ###-#### Inspection requested via web by Todd Hall...ok to final
ELE18-00759 Final6/25/20186/26/20186/26/2018 10:12:04 AMAPASS
Phone #: ###-#### Inspection requested via web by Todd Hall....ok to final
ELE18-00840 Final6/25/20186/26/20186/26/2018 10:11:28 AMAFAIL
Phone #: ###-#### Inspection requested via web by Todd Hall...boxes shall be flush with wall or tile...outlet needs installed completely...kitchen outlet no tile
ELE17-04126 Final6/25/20186/26/20186/26/2018 10:10:14 AMAPASS
Phone #: ###-#### Inspection requested via web by Todd Hall...ok to final
ELE12-01841 ELE-Aging Inspection6/26/20186/26/20186/26/2018 8:29:00 AM CANC
DOC expired
ELE18-00834 Final6/25/20186/26/20186/26/2018 8:24:12 AMAPASS
Phone #: ###-#### Inspection requested via web by Todd Hall...corrections made..ok to final
ELE18-00529 Final6/25/20186/26/20186/26/2018 8:16:39 AMAPASS
Phone #: ###-#### Inspection requested via web by Todd Hall...corrections made...ok to final