Inspections for the day of: Tuesday, June 26, 2018.
Number of inspections: 11
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorTroy Cobbley
TitleFIRE INSPECTOR
Phone #794-9483
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
FIR18-00094 INSP-Final Inspection6/25/20186/26/20186/26/2018 3:34:00 PMAFAIL
Need Lee to approve as-builts when received.

Rand Phone #: ###-####
BLD18-00955 FIRE-Conference6/26/20186/26/20186/26/2018 2:59:08 PMPDONE
I spoke with the project superintendant about the drawing sheet E4 that shows a fire alarm notification device and a manual pull station.
BLD17-02479 FIRE-Final Inspection6/26/20186/26/20186/26/2018 1:55:16 PMPPASS
Life safety passed. I let Pat know that the Grading Permit has not been signed off yet.


Pat Phone #: ###-####
BLD17-00022 FIRE-Final Inspection6/26/20186/26/20186/26/2018 1:52:43 PMPFAIL
See the city approved fire life safety notes for items that need corrected which include signage, repair one exit sign, final on fire alarm permit, painting on curbing...ect.


Tyler Phone #: ###-####
FIR18-00442 INSP-Sprinkler Rough-in6/26/20186/26/20186/26/2018 1:19:56 PMPPASS
Rough-in passed. Piping can be covered.

Adam Phone #: ###-####
FIR18-00448 INSP-Sprinkler Rough-in/Hydro6/25/20186/26/20186/26/2018 11:54:29 AMAPART
The rough-in for the mains and branchlines passed. Missing one earthquake brace at the drop down to the clean room. Need as-builts due to two addtional 90's in the 4" feed main just outside of the riser room. Will need another rough to cover inspection when the flex heads are installed. Not able to do the hydro test due to fhe flex heads not being installed.


Call Anthony to coordinate, thanks Phone #: ###-#### Inspection requested via web by Anthony Minichiello
FIR17-00412 INSP-Sprinkler Rough-in6/25/20186/26/20186/26/2018 10:21:04 AMAPART
Rough-in passed/piping can be covered. See the city approved plans for locations where several uprights need to be added and a large corridoe that the three pendant heads are overs paced

Phone #: ###-#### Inspection requested via web by Stan Beus
FIR18-00057 INSP-Sprinkler Rough-in6/25/20186/26/20186/26/2018 10:18:45 AMAPART
Pendant heads exceed 7' from wall in acouple locations. Final locations of these heads can be verified at final. Piping is ok for cover/rough-in passed.

Phone #: ###-#### Inspection requested via web by Stan Beus
FIR17-00522 INSP-Final Inspection6/25/20186/26/20186/26/2018 10:16:26 AMAPASS
Permit finaled

Phone #: ###-#### Inspection requested via web by Matthew Lewis
NAF16-00069 INSP-Sprinkler Rough-in/Hydro6/25/20186/26/20186/25/2018 12:00:00 AMACANC
There is no fire sprinkler system in the single family dwelling. Call prior to going >> Inspection requested via mobile web by Parkway
NAF16-00069 INSP-Final6/25/20186/26/20186/25/2018 12:00:00 AMAPASS
Verified that addess has been up dated with the fire department. Ron Johnson verified that he has recieved the update. 6-25-18**ajs**>> Inspection requested via mobile web by Parkway