Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
MEC18-01668 Final6/26/20186/26/20186/26/2018 5:04:11 PMPPART
partial final with air balance report/ email stating when exhaust fans will be worked on and rebalanced/ extend flue on rtu up 3' above economizer - email of when new exhaust fans will be in place ok- air balance of exhaust systems at current state - EF 1 and EF 2 are below 80% and will need to be rebalanced for complete final- snorkel flue 3' above economizer ok
MEC18-02959 Final6/25/20186/26/20186/26/2018 4:09:51 PMPPASS
INSTALLER TRAVIS ###-#### Phone #: ###-#### Inspection requested via web by Aaron Alandt- furnace ac coil co ok
MEC18-02977 Final6/25/20186/26/20186/26/2018 3:26:20 PMPPASS
INSTALLER BRANDAN ###-#### Phone #: ###-#### Inspection requested via web by Aaron Alandt- A/C coil co ok
MEC18-02728 Pressure Test6/26/20186/26/20186/26/2018 1:47:12 PMPPART
EARLY P.M. Inspection requested via web by Aaron Alandt- 20lb gas pressure test ok stickered meter bar- water heater 5lb flue test ok- furnace 5lb flue test failed gauge was at 5lb when i arrived but had dropped below 5lb while i checked the rest of the job
MEC18-02728 Rough-in6/26/20186/26/20186/26/2018 1:44:16 PMPPART
EARLY P.M. Inspection requested via web by Aaron Alandt- transfer airs ok- ductboard return sealed ok- the furnace flue 5lb test failed gauge was below 5lb- water heater 5lb flue test ok- 20lb gas pressure test ok stickered meter bar- need to see furnace flue pressure test and need to see that fireplace installers pull a MEC permit before i approve this permit for full R/I cover
MEC18-02922 Final6/25/20186/26/20186/26/2018 12:51:51 PMAFAIL
can you call when you are on the way. Customers name is Susan. Phone #: ###-#### Inspection requested via web by Marisa Hone- need a insulation sheild around furnace flue in attic above insulation level
MEC18-02985 Final6/25/20186/26/20186/26/2018 12:35:26 PMAFAIL
Gae Peyon (Bonnie with Air Care called in inspection but owner is contact) Phone #: ###-#### - exhaust fans not done- some supplys in crawl not finished- call in for a R/I when ready not a final
MEC18-01668 Final6/25/20186/26/20186/26/2018 11:42:33 AMANR
please call half prio Phone #: ###-#### Inspection requested via web by thomas nguyen
-scheduled a pm inspection- waiting on information and a fews things to be fixed by this afternoon
MEC17-03221 Mec-Aging Inspection6/26/20186/26/20186/26/2018 11:14:54 AM DONE
called advanced to have them schedule a final inspection with the homeowner
MEC18-02951 Pressure Test6/22/20186/26/20186/26/2018 11:01:51 AMAPASS
please call homeowner Louis when 30 mins in route for gas pressure test. Phone #: ###-#### Inspection requested via web by Rick Montgomery- 20 lb gas pressure test ok- need to see inert tape at gas line penetration at furnace final
MEC17-05401 Rough-in6/25/20186/26/20186/26/2018 10:37:12 AMAPART
Phone #: ###-#### Inspection requested via web by Nicholas Paige- 2nd floor stairwell NW corner hardlid ok for cover- downstairs 95% done just need to finish one return tie in and finish insulating returns- a few linesets on 1st floor need insulation finished
MEC17-04565 DOC - Permit Finaled6/26/20186/26/20186/26/2018 10:13:39 AMPPASS
furnace ac coil co ok
MEC17-03322 Mec-Aging Inspection6/26/20186/26/20186/26/2018 10:11:55 AM DONE
The equipment at this address is not a new install . I called Daves heating and air to find out more information on if they installed new equipment or not.
MEC17-04565 Mec-Aging Inspection6/26/20186/26/20186/26/2018 9:50:45 AM PASS
homeowner was home and let me in- furnace ac coil co ok
MEC18-02930 Final6/22/20186/26/20186/26/2018 9:27:28 AMAPASS
Contact Erika: ###-#### Phone #: ###-#### Inspection requested via web by Frank Marturello- furnace ac coil co ok
MEC18-02936 Final6/25/20186/26/20186/26/2018 9:06:09 AMAPASS
Jeff-please call 15 minutes prior to meet for access Phone #: ###-####- A/C coil final ok
MEC17-03306 Mec-Aging Inspection6/26/20186/26/20186/26/2018 8:30:30 AM NH
left notice on front door