Inspections for the day of: Wednesday, June 26, 2019.
Number of inspections: 14
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorJack Reynolds
TitleMEC INSPECTOR
Phone #208-803-2395
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
MEC19-02752 Pressure Test6/25/20196/26/20196/26/2019 4:01:42 PMPPASS
Please schedule in the afternoon - installing new equipment in the morning and call Carl (###-####) 30 minutes prior to showing up.
Please do Pressure Test and Final Inspection at same time.
If unable to reach Carl please call Michele @ ###-####.
Thank you. Phone #: ###-#### Inspection requested via web by Michele Johnson
- 5lb flue pressure test ok
- call in final when ready
- existing condensate line was tapped into drain in basement and cant be ran outside due to freezing temp in winter. contractor onsite said most likely a plumber would take care of condensate line. will need to see plumbing permit pulled for final
MEC19-00819 Final6/26/20196/26/20196/26/2019 3:30:34 PMPPASS
RUSSELL IS THE JOB CONTACT ###-#### Phone #: ###-#### Inspection requested via web by BECCA DUMMER
- final ok
- no occ card onsite to sign
MEC19-00819 Card not on site to sign6/26/20196/26/20196/26/2019 3:30:20 PMPPASS
RUSSELL IS THE JOB CONTACT ###-#### Phone #: ###-#### Inspection requested via web by BECCA DUMMER
- no card onsite pass
MEC19-02711 Final6/24/20196/26/20196/26/2019 2:50:18 PMPPASS
installer Nick ###-#### Phone #: ###-#### Inspection requested via web by Aaron Alandt
- furnace ac coil co ok
MEC19-01824 Final6/25/20196/26/20196/26/2019 2:03:38 PMPNR
Please call Kyle to ensure install is complete. Thank you! ###-#### Phone #: ###-#### Inspection requested via web by Rick Borg
MEC19-02742 Final6/25/20196/26/20196/26/2019 1:42:23 PMPPASS
Phone #: ###-#### Inspection requested via web by Marisa Hone
- furnace ac coil co ok
MEC19-01212 Rough-in6/25/20196/26/20196/26/2019 11:30:24 AMAPART
partial inspection on Heat Water System Josh ###-#### Phone #: ###-#### Inspection requested via web by RM Mechanical
- area A 100lb hydronics pressure test ok
MEC19-01845 Rough-in6/25/20196/26/20196/26/2019 10:31:38 AMAFAIL
Code 2390 Phone #: ###-#### Inspection requested via web by Ashley Shoecraft
- need to see non combustibles installed on top and sides of fireplaces
- bedroom fireplace has combustibles touching vent
- need to see gas lines stubbed into fireplaces
MEC19-01700 Rough-in6/25/20196/26/20196/26/2019 9:54:40 AMAPART
PART Phone #: ###-#### Inspection requested via web by Oleg Chervak
- east side bld K duct seal and R/I ok
MEC19-01022 Final6/25/20196/26/20196/26/2019 9:23:54 AMACANC

MEC19-01022 Rough-in6/26/20196/26/20196/26/2019 9:23:18 AMAPASS
partial final for Units:135, 136, 233, 234, 235, and 236.
Phone #: ###-#### Inspection requested via web by Nicholas Paige
- 135,136,233,234,235,236 R/I ok
call final when units are finished
MEC19-02272 Pressure Test6/25/20196/26/20196/26/2019 8:55:18 AMAFAIL
Phone #: ###-#### Inspection requested via web by Nicholas Paige
- high pressure test needs to be on 100lb gauge
- gas piping penetration needs protective coating
MEC18-03260 Mec-Aging Inspection6/26/20196/26/20196/26/2019 8:21:40 AM PASS
Doc Expire ok permit was not active
MEC18-03260 DOC - Permit Expired6/26/20196/26/20196/26/2019 8:20:31 AMAPASS
permit not active doc expire ok